User manual

5
E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT)
Model
Rotary
Switch
3-Bit
No. 3
2-Bit 1/2
ZX0200/E-PFJ 7 OFF ON/ON
ZX0250/E-PFJ 8 OFF ON/ON
ZX0300/E-PFJ 9 OFF ON/ON
ZX0400/E-PFJ A OFF OFF/OFF
ZX0200/E-TFD 1 OFF ON/ON
ZX0300/E-TFD 2 OFF ON/ON
ZX0400/E-TFD 3 OFF ON/ON
ZX0500/E-TFD 4 OFF ON/ON
ZX0600/E-TFD 5 OFF ON/ON
ZX0750/E- 760/E-TFD 6 OFF ON/ON
ZX0200/E-TF5 1 ON ON/ON
ZX0300/E-TF5 2 ON ON/ON
ZX0400/E-TF5 3 ON ON/ON
ZX0500/E-TF5 4 ON OFF/OFF
ZX0600/E-TF5 5 ON OFF/OFF
ZX0750/E- 760/E-TF5 6 ON OFF/OFF
ZX0200/E-TF7 7 ON ON/ON
ZX0300/E-TF7 8 ON ON/ON
ZX0400/E-TF7 9 ON ON/ON
ZX0500/E-TF7 A ON ON/ON
ZX0600/E-TF7 A ON ON/ON
ZX0750/E- 760/E-TF7 B ON ON/ON
ZXL0200/E-TFD 1 OFF ON/ON
Notes: The settings given in the table are pre-set at the factory for new units.
ON
1 2 3
OFF: Evaporator fan ON/OFF logic is same
as compressor and this is the factory
default setting.
ON: Evaporator fan will be ON for all time
irrespective of whether the compressor is
turned ON or OFF
Not applicable
Use setting in the table
Model
Rotary
Switch
3-Bit
No. 3
2-Bit 1/2
ZXL0250/E-TFD 2 OFF ON/ON
ZXL0300/E-TFD 3 OFF ON/ON
ZXL0350/E-TFD 4 OFF ON/ON
ZXL0400/E-TFD 5 OFF ON/ON
ZXL0500/E-TFD 6 OFF ON/ON
ZXL0600/E-TFD 7 OFF ON/ON
ZXL0750/E-TFD 8 OFF ON/ON
ZXL0200/E-TF5 1 ON ON/ON
ZXL0250/E-TF5 1 ON ON/ON
ZXL0300/E-TF5 2 ON ON/ON
ZXL0350/E-TF5 3 ON OFF/OFF
ZXL0400/E-TF5 4 ON OFF/OFF
ZXL0500/E-TF5 5 ON OFF/OFF
ZXL0600/E-TF5 6 ON OFF/OFF
ZXL0750/E-TF5 7 ON OFF/OFF
ZXL0200/E-TF7 8 ON ON/ON
ZXL0250/E-TF7 8 ON ON/ON
ZXL0300/E-TF7 9 ON ON/ON
ZXL0350/E-TF7 A ON ON/ON
ZXL0400/E-TF7 B ON ON/ON
ZXL0500/E-TF7 C ON ON/ON
ZXL0600/E-TF7 D ON ON/ON
ZXL0750/E-TF7 D ON ON/ON