Location and fixing
The unit should always be installed in a location that ensures clean air flow. It is recommended that a clearance of 300 mm
from the wall (or the next unit) be maintained from the unit’s left and rear panels whereas a clearance of 500 mm must be
maintained from the unit’s right, top and front panels (seen facing the front of the unit). Both service access and airflow
have been considered in making these recommendations. Where multiple units are to be installed in the same location, the
contractor needs to consider each individual case carefully. There can be many variations of unit quantities and available space
and it is not the intention of this manual to go over these. Ideally, the unit should be mounted on a solid concrete slab with
anti-vibration pads between unit feet and concrete. However the ZX condensing unit has also been designed for wall mounting
on suitable brackets. Wall mounting brackets are not included. Another factor to consider in finding a good installation site is
the direction of the prevailing wind. For example if the air leaving the condenser faces the prevailing wind, the air flow through
the condenser can be impeded, causing high condensing temperatures ultimately resulting in reducing unit life. A baffle is a
remedy for this situation.
Dual Fan Unit
4 to 7.6 HP
388
110
580
2-R7.5MM GROOVE
70
70
1242
500300
500
1029
23
172
90
300500
Liquid
Service Valve
Suction
Service Valve
Power
Supply Hole
424
94
352
2 Holes 15mm DIA
Single Fan Unit
2 to 4 HP
840
500
500
300
7070
23
1029
300500
Power
Supply Hole
Suction
Service Valve
Liquid
Service Valve
90
172
424
352
94
388
110
580
2-R7.5MM GROOVE
2 Holes 15mm DIA
Fixing dimensions and distances - Single fan unit
Fixing dimensions and distances - Dual fan unit