ZX Platform Condensing Unit User Manual
Index Disclaimer............................................................................................................................................ 1 Introduction To ZX Platform CDU......................................................................................................... 1 Receiving Your Unit............................................................................................................................... 1 Features And Value...............................................
ZX Platform CDU Disclaimer Thank you for purchasing the ZX platform condensing unit from Emerson Climate Technologies. ZX platform CDUs are the best in class within the capacity and operating range available in the market. ZX CDU is designed to operate reliably and to deliver high operating efficiencies in medium and low temperature refrigeration applications. It also provides constant monitoring of the compressor operating conditions and displays the running or fault conditions of the CDU.
ZX Platform Condensing Unit Diagnostic Protection Increased Reliability and Lower Maintenance Costs Flexibility More Installation Options Highest Efficiency Lower Energy Bills ZXD Series ZX and ZXL Series Proprietary Electronic Algorithms to Control Fan Speed, Optimizing Energy Performance for Local Seasonal Ambient Temperatures - Shuts down unit during failure - With real time monitoring of compressor operating conditions Built-in ZX Platform Controller Diagnostic Digital Messaging Variable Spee
Physical Layout The following figures give an introduction to the physical layout of the ZX Platform CDU. Figure 02: Identifies the Electronic controller assembly on a ZX platform CDU. ZX- MT, ZXL-LT E2 Controller * ZXD Digital Scroll Controller Scroll Compressor * ZXD Digital scroll controller not shown in Fig. 02. See Fig. 05 for LED and keypad Figure 03: Identifies other major components layout on a ZX platform CDU.
ZX Platform Condensing Unit Figure 05: Shows LED and keypad of ZXD digital scroll controller.
E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT) Model Rotary Switch 3-Bit No.
ZX Platform Condensing Unit Defrost Module Function Set Time of Defrost Time of Defrost Interval Rotary Switch1 Time(min) Rotary Switch2 Time (hours) 0 1 2 3 4 5 6 7 0 5 10 15 20 25 30 35 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 Defrost Duration (in Minutes) Manual Defrost Button Remote Connector For Manual Defrost Defrost Interval (In Hours) E2 Connector Figure 06 Figure 06: ZX Platform Defrost Module Digital Scroll controller (ZXD) The controller has been pre-programmed with a number of parameter val
Installation Copeland ZX condensing units are delivered with a holding charge of neutral gas. The condensing unit should be located in such a place to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins. The unit must be installed without restricting the airflow. A clogged condenser will increase the condensing temperature, thus reduce the cooling capacity, and lead to a high-pressure switch tripping. Clean the condenser fins on a regular basis.
ZX Platform Condensing Unit Refrigeration connections Refrigeration piping installation All interconnecting pipes should be of refrigeration grade, clean, dehydrated and must remain capped at both ends until installation. Even during installation, if the system is left for any reasonable period of time (say two hours), pipes should be recapped to prevent moisture and contaminants from entering the system.
Location and fixing 1029 500 Power Supply Hole Suction Service Valve Liquid Service Valve 2 Holes 15mm DIA 94 300 70 70 90 23 172 110 840 300 352 388 500 The unit should always be installed in a location that ensures clean air flow. It is recommended that a clearance of 300 mm from the wall (or the next unit) be maintained from the unit’s left and rear panels whereas a clearance of 500 mm must be maintained from the unit’s right, top and front panels (seen facing the front of the unit).
ZX Platform Condensing Unit Start Up and Operation Before commissioning, ensure that all valves on the condensing unit are fully opened. Evacuation The evacuation procedure is based upon achieving an actual system vacuum standard and is not time dependent. Before the installation is put into commission, it has to be evacuated with a vacuum pump. Proper evacuation reduces residual moisture to 50ppm.
Diagnostic messaging - LED definition (ZX-MT and ZXL-LT) LED1-Unit Status Display Controller Pause Unit Automatic Reset LED2-Error/Warning Code Display Status Display Warning Signal Error/Warning Controller Lock Unit Manual Reset Idle (Stop When Reach To Set-point) No error/warning Run Compressor Phase Error (Wrong Phase Sequence/Loss of Phase) Every Protection Action Every Protection Action NA About To Start 1 Compressor Inside Thermal Protector Trip Every Protection Action NA NA Defrost
ATTENTION: Unit MUST be grounded! PFJ: 220V-50 Hz -1Ph BLUE ZX Condensing Unit Wiring Diagram ZX Platform Condensing Unit 12
13 ATTENTION: Unit MUST be grounded! TFD: 380V/420V -50 Hz-3Ph TF7: 380V-60 Hz -3Ph ZX/ZXL Condensing Unit Wiring Diagram 5.Only ZXL TF5 has 4 additional posts on the terminal block.
ATTENTION: Unit MUST be grounded! TF5: 200/230V- 50 Hz/ 60 Hz - 3Ph ZX/ZXL Condensing Unit Wiring Diagram ZX Platform Condensing Unit 14
15 1 E E M2 M1 Black White 10 15 16 22 23 24 12 Capacitor2 White Black White Capacitor1 White Fan Speed Controller 3 2012-02-15 ATTENTION: Unit MUST be grounded! 052-2662-00 TF7 - 380V, 60Hz, 3Ph E L1 L2 L3 2 1 2 Internal motor protector T3(W) COMP'R T1(U) Red Yellow Red Red Blue Black Crankcase Heater T2(V) A2 22N/C T1 T2 T3 Black N N Fuse (2A/250V) 6 5 W Contactor 4 3 1 Blue Aux 21N/C Black A1 Red Blue Yellow Circuit Breaker "I" V U TFD: 380V/420V -
E E 2012-03-28 052-2677-00 Red M2 Red M1 To N To N White Capacitor2 White Black White Capacitor1 White Black ATTENTION: Unit MUST be grounded! TFD - 380/420V, 50Hz, 3Ph TF7 - 380V, 60Hz, 3Ph E L1 L2 L3 2 1 2 Internal motor protector T3(W) COMP'R T1(U) Yellow Red Red Red Blue Black Crankcase Heater T2(V) A2 22N/C T1 T2 T3 Black N N Fuse (2A/250V) 6 5 W Contactor 4 3 1 Blue Aux 21N/C Black A1 Red Blue Yellow Circuit Breaker "I" V U Input: 230VAC TFD: 380V/4
Contact List Emerson Climate Technologies Asia Pacific Headquarters 10/F, Pioneer Building, 213 Wai Yip Street, Kwun Tong, Kowloon, Hong Kong Tel: (852) 2866 3108 Fax: (852) 2520 6227 Australia Emerson Climate Technologies Australia Pty Ltd Unit R7, 391 Park Road Regents Park, NSW 2143, Australia Tel: (61-2) 9795 2800 Fax: (61-2) 9738 1699 India - Mumbai Emerson Climate Technologies (India) Ltd Unit No. 4,5,6 & 7, Bhaveshwar Arcade LBS Marg, Opp.