Technical information

2 C6.1.7/0609-1110/E
1.3 General instructions
WARNING
System breakdown! Personal injuries! Never install a system in the field
and leave it unattended when it has no charge, a holding charge, or with the
service valves closed without electrically locking out the system.
System breakdown! Personal injuries! Only approved refrigerants and
refrigeration oils must be used.
WARNING
High shell temperature! Burning! Do not touch the compressor until it has
cooled down. Ensure that other materials in the area of the compressor do
not get in touch with it. Lock and mark accessible sections.
CAUTION
Overheating! Bearing damage! Do not operate compressors without
refrigerant charge or without being connected to the system.
IMPORTANT
Transit damage! Compressor malfunction! Use original packaging. Avoid
collisions and tilting.
The contractor, responsible for the installation of the unit, should ensure sufficient liquid sub-
cooling in the line to the expansion valve(s) to avoid “flash-gas” in the liquid line.
It is of vital importance that the discharge stop valve has been fully opened before the
compressor is started. If the discharge stop valve is closed or partly closed an unacceptable
pressure with accordingly high temperatures may develop on the discharge outlet in the
compressor. When operating with air the so-called diesel effect may occur, ie, the air sucked in
is mixed with oil gas and can explode due to the high temperature, and thereby destroy the
compressor.