leads should not be moved or extended because
of the possibility of inducing electronic noise into
the INT69SCY, which could cause false trips of the
module.
Module and Sensor Functional Check
The following fi eld troubleshooting procedure can be
used to evaluate the solid state control circuit: Refer to
Table 6 for a technical data summary.
Module Voltage Supply Troubleshooting
Verify that all wire connectors are maintaining
a good mechanical connection. Replace any
connectors that are loose.
Measure the voltage across T1-T2 to ensure
proper supply voltage.
Determine the control voltage by using a voltmeter
and then measure the voltage across the M1-M2
contacts:
If the measured voltage is equal to the control a.
volts then the M1-M2 contacts are open.
If the measurement is less than 1 volt and the b.
compressor is not running, then the problem
is external to the INT69SCY or INT69SU
module.
If the voltage is greater than 1 volt but less than c.
the control voltage, the module is faulty and
should be replaced.
Sensor Troubleshooting
Remove the leads from S1-S2, and then by using
an ohmmeter measure the resistance of the
incoming leads.
CAUTION: Use an Ohmmeter with a maximum
TABLE 6
Emerson P/N 071-0520-07 071-0520-05 071-0620-00 071-0641-00
Manufacturer P/N T.I. 30AA201E Kriwan 69SC-DV Kriwan 69SCY Kriwan 69SU
T1-T2 Module Power
Voltage Supply 120V & 240V 120V & 240V 120V & 240V 120V & 240V
Frequency 50Hz & 60Hz 50Hz & 60Hz 50Hz & 60Hz 50Hz & 60Hz
M1-M2 Module Output Contacts
Maximum Voltage N/A 250VAC 250VAC 250VAC
Maximum Current 5 Amps 5 Amps 5 Amps 5 Amps
Minimum Current 100 milliamps 100 milliamps 100 milliamps 100 milliamps
Relay Output 2.5 A, 600 V 5 A, 300 VA 5 A, 300 VA 5 A, 300 VA
Power Output < 5.5 VA <3 VA <3 VA <3 VA
S1-S2 Thermal Protection
Trip Out Resistance N/A 4500W ± 20% 4500W ± 20% 4500W ± 20%
Reset Resistance N/A 2750W ± 20% 2750W ± 20% 2750W ± 20%
Reset Time 30 min ± 5 min 30 min ± 5 min 30 min ± 5 min 30 min ± 5 min
Manual Reset T1-T2 interrupt for
minimum of 5 sec
T1-T2 interrupt for
minimum of 5 sec
T1-T2 interrupt for
minimum of 5 sec
T1-T2 interrupt for
minimum of 5 sec
L1-L2-L3 Phase Monitoring
Phase Sensor Non Phase Sensing Non Phase Sensing 3 Non Phase Sensing
Phase Monitoring
Circuit Rating
Non Phase Sensing Non Phase Sensing 3 AC 50/60Hz
120V to 632V
Non Phase Sensing
Trip Delay Non Phase Sensing Non Phase Sensing 5 min delay before
restart attempt
Non Phase Sensing
Lockout Non Phase Sensing Non Phase Sensing After 10 module trips Non Phase Sensing
Reset For Lockout Non Phase Sensing Non Phase Sensing T1-T2 interrupt for
minimum of 5 sec
Non Phase Sensing