Specifications
24 • XR35CX I&O Manual 026-1203 Rev 0 09-FEB-2011
3. Press + to open the Serial tab of the General
Controller Info setup screens:
4. This screen will have a “Connection” field for all
COM ports on the E2. Highlight the COM port con-
nection field that will be used for the device, and
press
- LOOK UP. From the list of network
types, select MODBUS.
5. Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
• Baud - Default setting is 19.2k. The baud rate set-
ting should be set to match the baud rate of the de-
vice (9600). (All devices connected to the same
COM port should be set to the same baud rate.)
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
• Stop Bits - Leave this field at the default value (1).
6. Press
to save changes and exit.
18.1.2.Add and Connect the Device
To enable communications between E2 and the
XR35CX units, the devices must be added and ad-
dressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
- Connected I/O Boards
and Controllers.
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the
Quantity field. (Max shows the maximum number
of devices allowed on the network.)
4. Press
to return to the Network Setup menu,
then select
- Network Summary.
5. Locate the units you added to the network list (press
and to scroll through the list). If desired, en-
ter a new name for each device in the Name field.
6. By default, each device in the network list has a
board number of 0. To set the address and begin
communication, choose the device and press
. In the list of MODBUS devices, choose the
address number corresponding to the XR35CX ad-
dress set up through the XR35CX front display, and
press
to select it. A window will open where
Figure 18-3 - Serial Communications Manager Screen
Figure 18-4 - Num Network Ctrls: NetSetup Screen
Figure 18-5 - Network Summary Screen