Specifications

The ON/OFF Function Parameters • 13
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
iLE Energy Saving cycle start during work-
days
(0 to 23 hr 50 min)
During the Energy Saving cycle, the setpoint is increased by the
value in HES so that the operation setpoint is SEt + HES.
dLE Energy Saving cycle length during
workdays
(0 to 24 hr 00 min)
Sets the duration of the Energy Saving cycle on workdays.
iSE Energy Saving cycle start on holidays. (0
to 23 hr 50 min)
dSE Energy Saving cycle length on holidays
(0 to 24 hr 00 min)
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
Ld1 to
Ld6
Workday defrost start (0 to 23 hr 50 min) These parameters set the beginning of the 6 programmable de-
frost cycles during workdays. (e.g., When Ld2 = 12.4 the second
defrost starts at 12:40 during workdays.)
Sd1 to
Sd6
Holiday defrost start (0 to 23 hr 50 min) These parameters set the beginning of the 6 programmable de-
frost cycles on holidays. (e.g., When Sd2 = 3.4 the second defrost
starts at 3:40 on holidays.)
NOTE:
To disable a defrost cycle, set it to not used. (e.g., If Ld6 = not used, the sixth defrost cycle is disabled.)
OTHER PARAMETERS
Adr Serial address (1 to 244) Identifies the controller address when connected to a MODBUS
compatible monitoring system.
pbC Type of probe Allows to set the kind of probe used by the controller:
Pt1 = Pt1000 probe
ntc = NTC probe
onF ON/OFF key enabling not used = disabled
oFF = enabled
ES = not set it
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display (optional)
dP4 Fourth probe display
rSE Real setpoint Shows the setpoint used during the energy saving cycle or during
the continuous cycle.
rEL Software release For internal use only.
Ptb Parameter table code Read only
Code Parameter Function
Table 7-1 - List of Parameters