Troubleshooting guide

85
Using Danfoss Transducers with 2783J qualified
boards
The analog boards used in the Vission and Vantage
panels after July 2003 have been modified to ac-
commodate the use of Danfoss transducers (VPN
2783J). These analog boards are denoted as “2783J
qualified” boards. The use of 2783J qualified boards
with Danfoss transducers require that scaling fac-
tors for the Danfoss pressure transducers be checked
and modified if necessary.
The scale factors for all transducers are located at a
specific Index location in Vission/Vantage database.
Refer to Figure 1. This table shows the proper scale
factors for each type of transducer as well as the
Index location of the scaling factor for each trans-
ducer.
N660 3950
Value* : The value 3950 shown is the Scale Factor for transducers manufactured by Ametek and
Setra. This does NOT include Danfoss transducers. If Danfoss transducers are being used with
2783J qualified boards, the “Value” at the Indexes shown above needs to be modified to 4297.
The procedure on the next page describes how to modify the scaling factor.
Figure 1. Transducer Index Table and Scale Factors
Vission and Vantage (VSS and SOI units) Vission (VRS units)
Transducer Index Value* Transducer Index Value*
Suction N658 3950 Suction N658 3950
Discharge N659 3950 Discharge N659 3950
Man/Filter Out N660 3950 Manifold N660 3950
Filter In N661 3950 Filter Inlet N661 3950
Filter Outlet (Retrofit) N664 3950
Vission and Vantage (Cool Compression units) Vantage (Recip)
Transducer Index Value* Transducer Index Value*
Suction N658 3950 Suction N658 3950
Discharge N659 3950 Discharge#1 N659 3950
Man/Filter Out N660 3950 Filter Out N660 3950
Filter Inlet N661 3950
Discharge#2 N662 3950
Oil Manifold N663 3950
Crankcase N664 3950
Modifications for Analog Board (Vission/Vantage after July 2003)