Troubleshooting guide

82
The values or options in the screen displays shown must be entered before start-up.
SYSTEM CONTROL LIMIT VALUES WORKSHEET
TIMER VALUES SYSTEM VALUES VALUE LIMITS DEFAULT VALUES
AT START CAPACITY DECREASE 0/999 SEC 15 SEC
CAPACITY INCREASE MOTOR ON 0/255 SEC 2 SEC
CAPACITY DECREASE MOTOR ON 0/255 SEC 2 SEC
CMP STARTER AUX CONTACT BYPASS 0/255 SEC 10 SEC
CAP INCREASE MOTOR OFF 0/255 SEC 20 SEC
CAP DECREASE MOTOR OFF 0/255 SEC 10 SEC
VOL SLIDE ADJ TIMER 0/255 SEC 20 SEC
MINIMUM CAP PRELUB TIME 0/255 SEC 5 SEC
RUN CYCLE OIL PRESS BYPASS 0/90 SEC 60 SEC
PRELUB PUMP TIME LIMIT 0/255 SEC 255 SEC
FLTR DIFF PR SAFETY CHANGEOVER 0/999 SEC 60 SEC
LO OIL SEP LEVEL BYPASS TIMER 0/120 SEC 60 SEC
AUTO RESTART AFTER POWER FAIL 1/240 MIN 5 MIN
OIL SEP TEMP SAFETY CHANGEOVER 0/15 MIN 5 MIN
LO OIL INJ TEMP SFTY CHANGEOVER 0/15 MIN 6 MIN
ANTIRECYCLE STRT TIMER (MIN) (1) 0/30 MIN 20 MIN
FORCE START LAG COMP (MIN) (2) 0/60 MIN 30 MIN
HOT STRTS/HR COUNTER (COUNTS) (1) 1/10 COUNTS 3 COUNTS
NOTES:
(1) Must be field set.
(2) Set only if Lead/Lag option is selected.
System Timer Values