Troubleshooting guide

46
· Unload Rate 1 – If the system pressure falls be-
low the Unload Rate 1 pressure setpoint for the
time specified in the Unload Rate 1 Timer, Central
Control will attempt to decrease the capacity of
the system.
·
Unload Rate 2 – If the system pressure fails be-
low the Unload Rate 2 pressure setpoint for the
time specified in the Unload Rate 2 Timer, Central
Control will attempt to decrease the capacity of
the system.
·
Stop – If the system pressure falls below the Stop
setpoint, Central Control will immediately try to
shut down the lowest priority lag compressor. If
there is only one compressor running, Central Con-
trol will shut down.
·
CAP Load TimersThese timers are directly re-
lated to the setpoint values described above. The
timers are the minutes and seconds that theCentral
Control algorithm will hold before deciding on an
action. The CAP Load Rate Timers are related to
the appropriate Load 1 and 2 increase setpoints
described above.
·
CAP Unload TimersThe Capacity Unload Rate
Timers are similar to the timers described above,
however, they work to decrease system capacity.
The CAP Unload Rate Timers are related to the
appropriate Unload Rate 1 and 2 decrease setpoints
described previously.
·
Machine Start Time – This timer is the time the
system will wait until another compressor is started
in an attempt to increase capacity.
·
Force Priority 1 Compressor On Checkbox -
When checked this will override other sequencing
logic and priority 1 compressor will always run.
Pressing the box alternating checks and unchecks
it.
Compressor Sequencing (Max 5 Compressors)