Troubleshooting guide

44
This screen allows the operator to setup a sequenc-
ing network. Currently, the MicroController is ca-
pable of sequencing 5 compressors. In order for a
MicroController to participate on the network, it must
have a unique address from the other Controllers on
the network. Duplicate node addresses are not al-
lowed. The node address of each is done through
the Setup menu.
The MicroController which will initiate all conver-
sation on the network MUST be defined as node 100.
This is defined as the “master” node. All other node
numbers should be in the range of 101 through 174.
Ethernet Peer To Peer – In addition to having
unique node addresses, all compressors on the
Ethernet network must have unique IP addresses
and unique names. These are entered from the
IP Address/Name screen, accessed from the
VILTER ONLY screen. The Ethernet IP ad-
dresses of each of the five compressors listed
are required to be:
Equipment: Ethernet IP Address
Cmp#1: 10.8.0.73
Cmp#2: 10.8.0.74
Cmp#3: 10.8.0.75
Cmp#4: 10.8.0.76
Cmp#5: 10.8.0.77
Note: IP addresses must be set prior to
themicrocontrollers being connected together.
The Compressor Sequencing screen only needs to
be setup on the “Master” node. The elements of this
screen are:
· EquipmentAllows the operator to select the
size of each compressor. This information is
used to make sequencing decisions based on the
CFM of the compressor. A valid size MUST be
chosen for a compressor to participate in se-
quencing. This field also allows the operator to
change the name of each of the five compres-
sors listed.
Note: Sequencing and Remote/Start-Stop can NOT fuction at the same time- Sequencing will over-ride
remote start/stop!
Compressor Sequencing (Max 5 Compressors)