Troubleshooting guide

38
· Capacity Decrease At StartAt compressor startup,
the capacity motor is held at minimum position for
this time period. After the timer expires, the slide is
free to move in accordance to the system demands.
· Compressor Starter Auxiliary Contact Bypass – This
timer is used to bypass the motor amperage input at
start. After the timer times out, the program deter-
mines if the motor starter has pulled in by testing the
amperage channel. If the program determines that
the starter did not “pull in”, then the compressor will
fail on “Motor Starter Fail” message.
· Volume Slide Adjustment Timer – This timer de-
termines the intervals the volume slide is adjusted.
If the volume slide is between 2½% & 7% away
from the desired volume ratio, the motor is pulsed
once toward the desired volume. If the volume
slide is more than 7% away from the desired value,
the volume slide motor is continuously energized
until the valve is within 2½% of the desired value.
If the actual position is within 2½% of the desired
value, no adjustment will be made.
Compressor Timer Setpoints
To change a timer setting,
you must “Logon to Edit”
first. Push the “Set”
button then push on the
timer setpoint value you
wish to change. After the
setpoint is changed, press
the “Refresh” button.
This will refresh the
“Current” window, which
shows the elapsed time of
the timers.