Vission Control Manual
Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral is grounded at the source. An equipment ground should also be run to the panel. *See Wiring Instructions and Diagrams before proceeding. Before start-up you need to enter all system values and options, see section on Setpoint Values.
Table of Contents Important Note ............................................................................................................ 3 STANDARD VILTER WARRANTY STATEMENT ............................................. 6 Operational Flow Chart ............................................................................................. 8 Operational Flow Chart (cont.) ................................................................................. 9 Wiring Instructions ..............................
Safety Failure Message ............................................................................................ 70 Supressor Kit Installation ........................................................................................ 73 Flash Card Installation Instructions ....................................................................... 74 Back Light Installation Instructions ....................................................................... 76 System Setpoints Alarms and Trips Work Sheet .....
STANDARD VILTER WARRANTY STATEMENT Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eighteen (18) months from the date of shipment from Seller s manufacturing plant or twelve (12) months from date of installation at the initial end users location, whichever occurs first.
Operational Flow Chart 8
Operational Flow Chart (cont.
Wiring Instructions 11
Wiring Instructions For Vission Only 5-1= Main Power to Panel 5-2= Heater #1 power 5-5= Heater #2 Power 12
Wiring Instructions For Vission Only Mandatory Wiring Step #2 Motor Starter Contactor Connection The contact to the pull in the motor starter contactor is a dry contact, place a "HOT" wire from the starter circuit on 7-1. Place the wire to energize the starter contactor on 7-2.
Wiring Instructions For Vission Only Mandatory Wiring Step #3 CON 1 Motor Starter Auxilary Contact "HOT" to 4-5 Wire to energize to 1-1 CON 2 CON 1 CON 3 CON 2 CON 3 CON 4 CON 4 CON 5 CON 5 CON 6 CON 7 CON 6 CON 7 View Inside Of Vission Panel 14 1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10 6-1 6-2 6-3 6-4 6-5 6-6 6-7 6
Wiring Instructions For Vission Only Mandatory Wiring Step #4 CON 1 Oil Pump Starter Connection "HOT" to 6-1 Wire to energize on 6-2 CON 2 CON 1 CON 3 CON 2 CON 3 CON 4 CON 4 CON 5 CON 5 CON 6 CON 7 CON 6 CON 7 View Inside Of Vission Panel 1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10 6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9
Wiring Instructions For Vission Only Optional Wiring Step #5 Auxiliary / Safety Wiring A determination by the user is to be made if this option will be used. If it is not used, insure that a jumper is installed between L 2-1 and 1-2 If this option is used, remove the jumper 2-1 to 1-2 and place the high level cutout (typically, other cutouts or an E-stop could be used) common wire on 2-1 and the normally closed wire to 1-2.
Wiring Instructions For Vission Only Optional Wiring Step #6 Remote Start Wiring CON 1 A determination by the user is to be made if this option will be used. If it is not used, insure that a jumper is installed between L 2-1 and 1-5. If this option is used, remove the jumper 2-1 to 1-5 and place the dry remote start contact common wire on 2-1 and the normally open wire to 1-5.
Wiring Instructions For Vission Only Optional Wiring Step #7 Setpoint #1/#2 Selection Wiring A determination by the user is to be made if this option will be used. This optional input does not need to be closed for the compressor to run no jumper is required.
Note Page 19
Wiring Diagram For Vission Only 20
Wiring Diagram For Vission Only 21
Main Screen The Main Screen This screen has been designed to give the operator an overall view of all operating parameters affecting the compressor package. This screen should always be displayed when maintenance items and setpoint items are not being performed. The date on the screen is updated every ½ second. Status information such as Alarms and Trips are displayed on the screen. This Screen contains buttons to navigate to setpoint, setup and maintenance screens.
Set Up Screen From the Main screen, touch the Setup button. After entering an authorized user name password, the screen pictured below will appear. ·Operator Name – This is the same list that appears in the login dialog. Names in this list can be selected for deletion. To change a name or password, you delete the name and enter a new name/password pair. The VILTER operator name cannot be deleted.
Set Up Screen · Anti-Recycle – The operator can select from the following AntiRecycle options: True, Accumulative, Modified, or Hot Starts. These select the strategy used to prevent excessive start/stop cycles of the compressor. Timers and counters used to enforce anti-recycling are adjusted and monitored in the Compressor Timer Settings screen, reached from the Menu screen. Help for the Timer Settings screen explains how the different settings and strategies operate.
Set Up Screen Log On, Off,or Save Changes Press Log on/Save Button and the above screen will appear. When altering setpoints, log on is necessary. Select appropriate user name and enter password to change setpoints. This screen is also used to backup and save setpoints by pressing (Backup Settings). After performing a “Back up Setting” operation, DO NOT power down the Vission/Vantage panel for atleast 1 minute. This will allow adequate time to insure all setpoints have been properly stored.
Maintenance Screen Touch Here From the Main screen touch the Maintenance button. “Service Item Required” message indicates that the compressor runtime hours has accumulated to a value - or a point- where service Maintenance is required. >From the main screen, press the “Maintenance” button. A chart will be shown to indicate what service is required - based on the number of hours the compressor has run.
Maintenance Screen This screen shows the chart of routine maintenance to be performed on the machine at hourly intervals from 200 hours to 120,000 hours. The Service Button from the Maintenance Screen will bring you to this screen. When entering service items that were completed, make sure to check all items that are listed to be done at that service interval.
Menu Screen At the bottom of the Main screen touch the Menu button to bring up the screen shown in Figure below. Use this screen to navigate to the other setpoint screens contained within the program. Each screen has a help button to describe the function of the screen.
Common Buttons A. Common Buttons There are several buttons that are common for all menu screens: · Return to Menu – This button always returns you to the Menu screen · Logon To Edit – The user is allowed to view data at all screen levels but cannot edit data until a login has occurred. In order to logon, press the arrow next to user name, select user then press the abc button, the key pad screen will appear. Enter your password and hit OK.
Compressor Control Level 1 Access – Compressor Control Setpoints From the Menu screen , press the Compressor Control setpoints button. The compressor control setpoints screen will be shown. These screens enable the operator to view and adjust settings that affect compressor control.
Compressor Control Setpoints on this screen: · · · · Suction Pressure On/Off – The compressor will automatically cycle ON and OFF at the setpoints entered. Suction Pressure On/Off control is only active if the Compressor Control Via Suction Pressure option is selected on the Setup screen. If a compressor shutdown is desired on a suction pressure drop and a manual reset is required, set the OFF value below the Low Suction Pressure Safety Trip value.
Additional Compressor Controls · · High Discharge Pressure Unloading Setpoints 1&2 – Active in Suction Pressure or Process Temperature Capacity Control mode. These setpoints limit the compressor from loading at high discharge pressure conditions. They override the Suction Pressure or Process Temperature Capacity Control setpoints. The capacity of the compressor will decrease when the discharge pressure is at or above the ON set point.
Compressor Control · Oil Separator Heater Temperature – This control limit determines when the oil separator heater is energized. A decrease in oil separator temperature below the ONsetpoint energizes the oil separator heater. On an increase in oil separator temperature above the OFF setpoint, the oil heater is de-energized. · Oil Pump Restart – To determine the ON and OFF values for the pressure ratios, take the absolute discharge pressure (PSIA), and divide it by the absolute suction pressure (PSIA).
· Low Suction Pressure Load Limit – Active in Discharge Pressure Capacity Control mode only. These setpoints limit the compressor from loading at low suction pressure conditions. They override the discharge pressure capacity control setpoints. When the OFF setpoint is reached (at or below setpoint), the compressor will not be allowed to load any further. If the suction pressure continues to fall, the capacity of the compressor will decrease when the suction pressure is at or below the ON set point.
Compressor Alarm and Trip · · Low Suction Pressure Setpoints 1&2 – This is the low suction pressure safety. This safety is active in both temperature and pressure control modes. An alarm or trip will be active on a drop in suction pressure below the setpoint value. · High Discharge Temperature – This is the high discharge temperature safety. The alarm or trip will be active if the discharge temperature should rise above the setpoint value.
Compressor Alarm and Trip setpoint. The alarm or trip will be active if the oil temperature of the separator drops below the setpoint value. · Low Oil Injection Temperature – This is the low oil injection safety. The alarm or trip will be active if oil injection temperature drops below setpoint value after a time delay (Oil Injection Temperature Safety Changeover). · High Oil Injection Temperature – This is the high oil injection temperature safety.
Compressor Setpoints and Alarms · · Prelube Oil Pressure – If the oil pressure does not rise above the reset setting for a time exceeding the Minimum Compressor Prelube Time and the pump runs longer than the Prelube Pump Time Limit, an alarm or trip will occur. These time limits are set on the Compressor Timer Setpoints screen. Prelube oil pressure is defined as the amount that the oil pump drives manifold pressure above the discharge pressure. Low Oil Pressure – This is the running oil pressure safety.
Compressor Timer Setpoints To change a timer setting, you must “Logon to Edit” first. Push the “Set” button then push on the timer setpoint value you wish to change. After the setpoint is changed, press the “Refresh” button. This will refresh the “Current” window, which shows the elapsed time of the timers. · Capacity Decrease At Start – At compressor startup, the capacity motor is held at minimum position for this time period.
Compressor Timer Setpoints · Minimum Compressor Prelube Timer – This is the length of time the oil pump will run after establishing the Prelube Oil Pressure, to prime oil circuit before starting the compressor. · Oil Pressure Bypass At Compressor Start – This timer bypasses the Low Oil Pressure limits. The timer starts when the compressor starts. After the timer has cycled, the Low Oil Pressure setpoint is active.
Compressor Timer Setpoints The compressor restart options (Hot Starts or Anti-Recycle Timers) are selected from the Setup screen. One additional Anti-Recycle Timer that can be selected from the Setup screen is the Modified Anti-Recycle Timer. · Modified Anti-Recycle Timer – Normally, this anti-recycle timer will function as a True AntiRecycle Timer.
Miscellaneous Screens (Condenser Control) This screen is designed for customized functions only, thus maybe placed as a view only screen. Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit. To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
Miscellaneous Screens (Motor Speed) This screen is designed for customized functions only, thus maybe placed as a view only screen. Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit. To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
Compressor Sequencing (Max 5 Compressors) From the Main Menu (press sequencing), this screen will appear. You must clear the IP Address before entering a new one.
Compressor Sequencing (Max 5 Compressors) Note: Sequencing and Remote/Start-Stop can NOT fuction at the same time- Sequencing will over-ride remote start/stop! This screen allows the operator to setup a sequencing network. Currently, the MicroController is capable of sequencing 5 compressors. In order for a MicroController to participate on the network, it must have a unique address from the other Controllers on the network. Duplicate node addresses are not allowed.
Compressor Sequencing (Max 5 Compressors) · Node – These node address fields tell the sequencing algorithm which the MicroController will be participating in the sequencing network. Input the node addresses of each Controller, participating on the network, in these fields. · · Max Cap – The Maximum Capacity is the highest capacity, in percentage, that this compressor is allowed to reach during operation.
Compressor Sequencing (Max 5 Compressors) · Unload Rate 1 – If the system pressure falls below the Unload Rate 1 pressure setpoint for the time specified in the Unload Rate 1 Timer, Central Control will attempt to decrease the capacity of the system. · Unload Rate 2 – If the system pressure fails below the Unload Rate 2 pressure setpoint for the time specified in the Unload Rate 2 Timer, Central Control will attempt to decrease the capacity of the system.
Vilter Only Screen WARNING: Settings on these screens should be used only by Vilter representatives or persons acting under their direction. Improper setting may result in loss of vital data and require service NOT covered under warranty.
Diagnostics Force Output · 48 On/Off – This will turn the force outputs option On/Off. The force outputs that can be modified are as follows: Main Motor Starter, Oil Pump, Economizer Solenoid, Remote Alarm/Trip, Liquid Injection Solenoid, Capacity Increase Motor, Capacity Decrease Motor, Volume Increase Motor and Volume Decrease Motor. You can choose the forced output by pressing the down arrow in the control labeled Available Outputs.
Instrument Calibration The current values reflect the values presently maintained by the system. The user can perform a one-point calibration by entering an offset value into the respective column. This will automatically adjust the current value and zero out the offset value. Giving max and min values for a respective current value can perform a two-point calibration. The program will automatically adjust the calibration line to meet those values.
Instrument Calibration Instrument calibration menu displays the Input channels that can be calibrated to represent the actual values at the sampling points. The current values reflect the values presently maintained by the system. The user can perform a one point calibration by entering an offset value into the respective column. This will automatically adjust the current value and zero out the offset value.
Calibration Procedure of Optical Actuators * If you are replacing or reinstalling a new optical actuator see: page 63 first. ACTUATOR MOTOR CONTROL MODULE CALIBRATION PROCEDURE 4. Press “Menu” on the main screen and then press the “Slide Calibration” button, to enter the slide calibration screen. If you are re-installing a new optical actuator re-connect the yellow and gray cables. 5. Press INC and DEC to move the slide valve and check for the correct rotation.
Calibration Procedure of Optical Actuators 7. Quickly press and release the blue push button on the actuator one time. This places the actuator in calibration mode. The red LED will begin flashing rapidly. 8. Note: When the actuator is in calibration mode, it outputs 0V when the actuator is running and 5V when it is still. Thus, as stated earlier, the actuator voltage will fluctuate during calibration.
Calibration Procedure of Optical Actuators 15. Now use the DEC and INC buttons to position the slide valve until a value close to 300 millivolts is on the screen. Then, press the “Set Min” button in the capacity or volume slide valve window to tell the controller that this is the minimum millivolt position. Note: The value in the “Current Cap” or “Current Vol” window has no meaning right now. 22. Gently lower the plastic cover over the top of the actuator to where it contacts the base and o-ring seal.
Installation Instructions For Replacement Of Optical Actuator CAUTION: WHEN INSTALLING THE OPTICAL SLIDE MOTOR, LOOSEN LOCKING COLLAR BEFORE SLIDING THE COLLAR DOWN THE SHAFT. DO NOT USE A SCREWDRIVER TO PRY LOCKING COLLAR INTO POSITION. OVERVIEW Calibration of an optical slide valve actuator is a two step process that must be down for each actuator installed on the compressor. The steps are as follows. 1.
Slide Valve Actuator Troubleshooting Guide Slide Valve Actuator Theory of Operation The slide valve actuator is a gear-motor with a position sensor. The motor is powered in the forward and reverse directions from the main computer in the control panel. The position sensor tells the main computer the position of the slide valve. The main computer uses the position and process information to decide where to move the slide valve next.
Slide Valve Actuator Troubleshooting Guide The actuator cannot be calibrated The actuator goes into calibration mode spontaneously The actuator goes into calibration mode every time power is restored after a power loss 56 Dirt or debris is blocking one or both optocoupler slots Clean the optocoupler slots with a Q-Tip and rubbing alcohol.
Slide Valve Actuator Troubleshooting Guide The actuator does not transmit the correct position after a power loss There is a rapid clicking noise when the motor is operating The motor operates in one direction only The motor will not move in either direction The motor runs intermittently, several minutes on, several minutes off The motor was manually moved while the position sensor was not powered. Recalibrate.
Slide Valve Actuator Troubleshooting Guide The motor runs sporadically The motor runs but output shaft will not turn 58 Bad thermal switch Replace the actuator. Any of the reasons listed in “The motor will not move in either direction” See above. Stripped gears inside the gear motor or the armature has come un-pressed from the armature shaft Replace the actuator.
Slide Wiring Diagram for Models Vission VSM-91 To VSS-601 59
Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801 60
Command Shaft Rotation and Travel COMMAND SHAFT ROTATION NO. OF TURNS / ROTATION ANGLE / SLIDE TRAVEL COMP. CAPACITY VOLUME CAPACITY VOLUME MODEL INC DEC INC DEC TURNS/ANGLE/TRAVEL TURNS/ANGLE/TRAVEL VSR 111 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 151 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 221 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 301 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSS 451 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers · IMPORTANT After the slide valves have contacted the internal stop, release the tension in the mechanism by actuating the brake and then manually turn the command shaft back one tooth on the command shaft gear. Failure to do so may result in premature failure of the gear motor.
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers and 1100 millivolts. Without changing the gear mesh, remove one ¼” screw, and apply Loctite #242 to the threads. Reinstall the screw finger tight, then repeat the procedure on the remaining screw (do not change the orientation of the lockwashers on the screws). The gear lash must be adjusted so there is no side load on the potentiometer shaft. Tighten and torque the ¼” socket head cap screw to 16 ft/lbs. Recheck the millivolt reading.
Trend Chart The trend analysis screen shows recorded data for a logging range of either 60 minutes or 120 hours. Additionally, selections can be made to display segments of the logged data. To view which selections are being shown hit the data select button. Note: When the panel is powered down, and powered back up, the “Trend Screen” will default to 120 hours even if you have chosen 60 minutes. Trend data is not retained.
Data Select Screen The user has the ability to select which value they would like to see displayed on the graph. Only four selections can be chosen at once to view, even though all data is being accumulated.
Event List Touch Here From the Menu screen, touch the Event List button. The screen on the next page will appear.
Event List The Event List will give a chronological record of the last 40 events recorded by the controller. These events can be filtered by selecting the Filter box on the upper left of the screen.
Trouble Shooting Flowchart (Vission Only) Check to make sure 120VAC is run to “L1” on the Relay board. This is the board on the inside left back of the panel. “L1” is the fifth connector down from the top and the top terminal. The neutral should be brought to any “N” on the relay board. MicroController does not boot up, no lights on any boards. MicroController appears to be booted, lights seen on boards and Estop switch, but no touch screen is evident. Check F1 fuse on relay board.
Trouble Shooting Flowchart (Vission Only) A bank of pressure or temperature channels no longer function. There are four fuses on the Analog board that limit the current on the 24VDC to the Analog channels. The fuses are 500 milliamp, located near the power supply connectors and brown in color. LEDs next to the fuses give a visual indication of the status of the fuse, however, it is best to pull the fuse and check them with an ohmmeter.
Safety Failure Message 70 Suction Pressure SP#1 Fail - This message will appear when the suction pressure falls below the safety setting of the Lo Suction Pressure Trip Setpoint No.1. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer or bad analog channel. Suction Pressure SP#2 Fail - This message will appear when the suction pressure falls below the safety setting of the Lo Suction Pressure Trip Setpoint No.2.
Safety Failure Message Percent Volume Fail – This message will appear if the percent volume reading exceeds 300% or goes below –15%. Lo Control Temperature Fail – This message will appear when the Process Control Temperature falls below the safety setting of the Lo Control Temperature Trip Setpoint. In addition, this message will appear when the Process Control Temperature rises above 300 degrees F, indicating an open RTD.
Safety Failure Message 72 Run Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above the High Fltr Diff Press – Run setpoint after the Filter Differential Pressure Safety Changeover timer times out. Maximum Amperage Fail – This message will appear if the motor amperage rises above the Hi Motor Amps trip setpoint.
Supressor Kit Installation 73
Flash Card Installation Instructions Note: Before Powering Down To Replace Flashcard, You Must Copy Down All Setpoints As These Will Need To Be Re-entered When New Flashcard Is Installed. Hit The Emergency Stop Botton Located In Front Of the Panel Verify Unit is Shut Down Completely VANTAGE/VISSION EMERGENCY STOP BUTTON Verify Lockout Disconnect On Compressor Start. This Ensures Compressor Does Not Start.
Flash Card Installation Instructions Press Latch To Release Flashcard Remove Flashcard And Replace Flip Board Back Into Postion Secure Board To Mounts With Previously Removed Screws Reconnect Connectors and Ribbons Note: You Must Re-enterSetpoints And Recalibrate SlideValves. See Section On Setpoint Values And the Section On Optical Actuators.
Back Light Installation Instructions Remove (Four) Nuts Remove Board Flip Board Over Unplug Connector Disconnect Ribbon Remove (Four) Screws And Turn Board Over 76
Back Light Installation Instructions Remove Small Screw And Slide Back Light Out As Shown Slide New Back Light In And Secure With Previously Removed Screw 77
Back Light Installation Instructions Place Board Back Into Postion And Secure Connect Ribbon And Plug Connector Back In Place Board Back Onto Back Of Panel And Secure With Previously Removed Nuts 78
Transducer Wiring 79
System Setpoints Alarms and Trips Work Sheet SAFETY SETPOINTS SYSTEM VALUES ALARM TRIP RESET VALUE LIMITS ALARM TRIP RESET DEFAULT VALUES ALARM TRIP RESET LO SUCTION TEMP -99/300 -99/300 -99/300 -45 -50 -40 HI DISCHARGE TEMP -30/260 -30/260 -30/260 205 210 200 LO OIL SEP START TEMP 50/200 50/200 50/200 75 70 80 LO OIL SEP RUN TEMP 50/200 50/200 50/200 105 100 110 LO OIL INJECT TEMP 50/160 50/160 50/160 95 90 100 HI OIL INJECT TEMP -99/160 -99/160 -99/160 140 14
System Control Limit Values Work Sheet SYSTEM CONTROL LIMIT VALUES WORKSHEET CONTROL LIMITS SYSTEM VALUES CUT IN CUT OUT SUCTION PRESSURE ON/OFF (1) SETPOINT #1 SETPOINT #2 SUCT PR CAP INCREASE (1) SETPOINT #1 SETPOINT #2 SUCT PR CAP DECREASE (1) SETPOINT #1 SETPOINT #2 HIGH DSCH PRESS UNLD (1) SETPOINT #1 SETPOINT #2 LIQ INJECTION SOLENOID CONTROL TEMP VIA: OIL INJECTION TEMPERATURE OIL SEPARATOR TEMPERATURE OILPMP RESTART (D/S) OIL SEPARATOR HEATER CAP CTRL °F ON/OFF (2) SETPOINT #1 SETPOINT #2 CAP CTR
System Timer Values The values or options in the screen displays shown must be entered before start-up.
RTD INTERNAL 4-20 mA EXTERNAL 4-20 mA DETAIL-B TRANSDUCER JUMPER CONFIGURATION STANDARD JUMPER SETTINGS DETAIL-A RTD JUMPER CONFIGURATION STANDARD JUMPER SETTINGS SEE DETAIL-B SEE DETAIL-A SUBPANEL LAYOUT EMERGENCY STOP micro-controller VISSION DOOR LAYOUT
Spare Parts PART DESCRIPTION VILTER PART NUMBER QTY.
Modifications for Analog Board (Vission/Vantage after July 2003) Using Danfoss Transducers with 2783J qualified boards The analog boards used in the Vission and Vantage panels after July 2003 have been modified to accommodate the use of Danfoss transducers (VPN 2783J). These analog boards are denoted as “2783J qualified” boards. The use of 2783J qualified boards with Danfoss transducers require that scaling factors for the Danfoss pressure transducers be checked and modified if necessary.
Modifications for Analog Board (Vission/Vantage after July 2003) The procedure to Change Scale Factors on 2783J Qualified Board 1. 2. 3. 4. 5. 6. 7. 8. From the Main Screen, press the Menu button. From the Menu Screen, press the Vilter ONLY screen. Logon From the Vilter ONLY screen, press the Raw Data Screen button. You will now see a screen labeled “Data Test”, containing 4 columns, 2 labeled “Index” and 2 labeled “Value”.
Danfoss Liquid Injection Valves 1. 2. 3. 4. 5. Press “Setup” Select “Enable” for Liquid Pos. Valve Press “OK” Press “Vilter Only”, you will be prompted to Log In Press “Liquid Inj. Temp Control” then you will see the screen as in the attached picture “Liquid Inj. Control”, the values you see there are default and can be changed according to your application. Setup Screen NOTE: Consult the VSS / VSM / VSR Unit Manual for proper Danfoss ICM valve setup procedure. Vilter Only Screen Liquid Inj.
Who to Contact If service is required, first contact your equipment distributor or contact A Vilter Technical Service Representative at: Vilter Manufacturing LLC 5555 South Packard Ave. PO Box 8904 Cudahy, WI 53110-8904 Tel: 414-744-0111 Fax: 414-744-1769 e-mail: info.vilter@emerson.com www.vilter.com Note: It will be necessary to have your Vilter order number available when contacting Vilter Manufacturing Corporation for service support.
EmersonClimate.com Vilter Manufacturing LLC P.O. Box 8904 Cudahy, WI 53110-8904 P 414 744 0111 F 414 744 1769 www.vilter.com Vilter Manufacturing LLC are trademarks of Emerson Electric Co. or one of its affi liated companies. ©2011 Emerson Climate Technoligies, Inc. All rights reserved. Printed in the USA.