Section 13 • Instruments Calibration
Remote Capacity
The remote capacity input allows a system controller
such as the PLC to control the capacity position during
direct I/O control.
Control Input:
• This dropdown box is not used at this time.
Scale:
• Defi nes the minimum and maximum Capacity posi-
tion between 0% & 100% for the 4-20ma input.
Offset:
• Used to correct any error in the capacity position. By
entering a value into the Adjustment entry box, that
value will be added to the total offset displayed in the
“total offset” entry box.
Analog Inputs
This section of the Calibration screen allows the opera-
tor to defi ne the parameters of an installed auxiliary ana-
log instrument. These instruments are usually not part
of a typical compressor setup but Vission 20/20 provides
a way for the operator to add additional capabilities. The
layout of this screen is typical to the pressure and tem-
perature calibration screens. For Analog Inputs screens,
see Figures 13-4 and 13-5.
Device Calibration:
• These setpoints allow the operator to defi ne what the
input from the auxiliary instrument means in terms
of units and range. If a temperature measuring in-
strument is connected, then the operator would se-
lect temperature from the Unit drop-down box then
set the maximum and minimum value for the scale.
Figure 13-4. Instruments Calibration Screen - Analog Inputs (Page 4)