Section 6 Compressor Control
Figure 6-10. Compressor Control Screen - Misc. 1 (Control Mode)
Control Mode
This drop down box gives the operator the ability to
change the type of control mode such as suction pres-
sure control or process temperature control. The opera-
tor can also switch from setpoint 1 and setpoint 2 for
each control method. What is available in this dropdown
box is dependent on the number and type of control se-
lected in the con guration screen, see Figure 6-10.
Stop Load and Force Unload
The stop load and force unload feature’s primary pur-
pose is to attempt to prevent the compressor from
tripping off due to particular instrument reading. For
example, if the suction pressure drops too low, the com-
pressor will trip off for safety reasons. However, the stop
load & force unload algorithm recognizes a potential trip
and either stops the compressor from loading up or even
unloads the compressor to prevent the trip.
Stop load:
When this value is reached, the capacity slide will not
advance in any condition.
Force Unload:
• When this value is reached, the capacity slide posi-
tion will decrease until the variable reading is below
this value.
High Motor Amps:
Motor current values for stop load and force unload.
High Discharge Pressure:
Discharge pressure value for stop load and force
unload.
Low Suction Pressure:
Suction pressure values for stop load and force unload
High Discharge Superheat:
Discharge temperature superheat values for stop
load and force unload. This is only used for Cool
Compression.