Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B Vission 20/20 Application Procedures
431 N69:46 41216 Step #2 Low Speed Fan
(Summer, Winter)
ENUM "0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
432 N69:47 41217 Step #3 Low Speed Fan
(Summer, Winter)
ENUM "0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
433 N69:48 41218 Step #4 Low Speed Fan
(Summer, Winter)
ENUM "0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
434 N69:49 41219 Step #5 Low Speed Fan
(Summer, Winter)
ENUM "0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
435 N69:50 41220 Condenser VFD Gain (P) F-INT Read-
Write
0.0 10.0
436 N69:51 41221 Condenser VFD Reset (I) F-INT Read-
Write
0.0 10.0
437 N69:52 41222 Condenser VFD Rate (D) F-INT Read-
Write
0.0 10.0
438 N69:53 41223 Condenser VFD Minimum
Speed (%)
INT Read-
Write
020
439 N69:54 41224 Condenser VFD
Maximum Speed (%)
INT Read-
Write
80 100
Con guration
(Time)
440 N76:0 41330 Time – Hours INT (HH) Read-
Write
023
441 N76:1 41331 Time – Min INT (MM) Read-
Write
059
442 N76:2 41332 Time – Secs INT (SS) Read-
Write
059
443 N76:3 41333 Date – Year INT (YYYY) Read-
Write
1970 2037
444 N76:4 41334 Date – Month INT (1-12) Read-
Write
112
445 N76:5 41335 Date – Day INT (1-31) Read-
Write
131