Appendix B • Vission 20/20 Application Procedures
387 N69:2 41172 High to Low Speed Fan
Delay (seconds)
INT Read-
Write
530
388 N69:3 41173 Condenser Setpoint F-INT Read-
Write
100.0 150.0
389 N69:4 41174 Upper Deadband F-INT Read-
Write
0.5 20.0
390 N69:5 41175 Lower Deadband F-INT Read-
Write
0.5 20.0
391 N69:6 41176 Wetbulb Offset F-INT Read-
Write
0.5 20.0
392 N69:7 41177 Switch Temp F-INT Read-
Write
25.0 45.0
393 N69:8 41178 Summer/Winter Auto
Switch Enabled
INT 0 = Disabled, 1 =
Enabled
Read-
Write
394 N69:9 41179 Wetbulb Override
Enabled
INT 0 = Disabled, 1 =
Enabled
Read-
Write
395 N69:10 41180 Step #1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
396 N69:11 41181 Step #2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
397 N69:12 41182 Step #3 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
398 N69:13 41183 Step #4 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
399 N69:14 41184 Step #5 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
400 N69:15 41185 Step #1 Out#1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
401 N69:16 41186 Step #2 Out#1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
402 N69:17 41187 Step #3 Out#1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
403 N69:18 41188 Step #4 Out#1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
404 N69:19 41189 Step #5 Out#1 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
405 N69:20 41190 Step #1 Out#2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
406 N69:21 41191 Step #2 Out#2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Re
ad-
Write
407 N69:22 41192 Step #3 Out#2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
408 N69:23 41193 Step #4 Out#2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
409 N69:24 41194 Step #5 Out#2 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write
410 N69:25 41195 Step #1 Out#3 Enabled
(Summer, Winter)
INT 0 = Disabled, 1 =
Enabled
Read-
Write