Service manual
B - 94
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B • Vission 20/20 Application Procedures
371 N67:82 41082 Saturday Event #4 Hour INT Read-
Write
(See
Notes)
023
372 N67:83 41083 Saturday Event #4 Minute INT Read-
Write
(See
Notes)
059
373 N67:84 41084 Comp Schedule Enable/
Disable
INT 0 = Disable, 1 =
Enable
Read-
Write
(See
Notes)
Compressor
Sequencing
374 N68:0 41100 Control Setpoint
(Pressure, Temp)
F-INT Read
375 N68:1 41101 Load Rate 1 offset
(Pressure, Temp)
F-INT Read-
Write
0.0 100.0
376 N68:2 41102 Load Rate 2 offset
(Pressure, Temp)
F-INT Read-
Write
0.0 100.0
377 N68:3 41103 Unload Rate 1 offset
(Pressure, Temp)
F-INT Read-
Write
0.0 100.0
378 N68:4 41104 Unload Rate 2 offset
(Pressure, Temp)
F-INT Read-
Write
0.0 100.0
379 N68:5 41105 Load Rate 1 Timer
(Pressure, Temp)
(seconds)
INT Read-
Write
0 10000
380 N68:6 41106 Load Rate 2 Timer
(Pressure, Temp)
(seconds)
INT Read-
Write
0 10000
381 N68:7 41107 Unload Rate 1 Timer
(Pressure, Temp)
(seconds)
INT Read-
Write
0 10000
382 N68:8 41108 Unload Rate 2 Timer
(Pressure, Temp)
(seconds)
INT Read-
Write
0 10000
383 N68:9 41109 Machine Start Time
(seconds)
INT Read-
Write
0 10000
384 N68:10 41110 Machine Stop Time
(seconds)
INT Read-
Write
0 10000
Condenser Control
385 N69:0 41170 Run Mode ENUM "0 = Run Never
1 = Run With Comp
2 = Run Always
3 = Manual"
Read-
Write
386 N69:1 41171 Profi le ENUM "0 = Summer
1 = Winter"
Read-
Write