Service manual
B - 85
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B • Vission 20/20 Application Procedures
Alarms/Trips
(Page 2)
241 N64:0 40800 Low Suction Temp. Alarm F-INT Read-
Write
-100.0 210.0
242 N64:1 40801 Low Suction Temp. Trip F-INT Read-
Write
-100.0 210.0
243 N64:2 40802 High Disch. Temp. Alarm F-INT Read
244 N64:3 40803 High Disch. Temp. Trip F-INT Read
245 N64:4 40804 Low Oil Sep. Start Temp.
Alarm
F-INT Read
246 N64:5 40805 Low Oil Sep. Start Temp.
Trip
F-INT Read
247 N64:6 40806 Low Oil Sep. Run Temp.
Alarm
F-INT Read
248 N64:7 40807 Low Oil Sep. Run Temp.
Trip
F-INT Read
249 N64:8 40808 Low Oil Inj. Temp Alarm F-INT Read
250 N64:9 40809 Low Oil Inj. Temp Trip F-INT Read
251 N64:10 40810 High Oil Inj. Temp Alarm F-INT Read
252 N64:11 40811 High Oil Inj. Temp Trip F-INT Read
253 N64:12 40812 High Oil Separator Temp
Alarm
F-INT Read
254 N64:13 40813 High Oil Separator Temp
Trip
F-INT Read
255 N64:14 40814 High Superheat Start
Temp Trip
F-INT Read-
Write
0.0 100.0
256 N64:15 40815 High Superheat Run
Temp Alarm
F-INT Read-
Write
21.0 23.0
257 N64:16 40816 High Superheat Run
Temp Trip
F-INT Read-
Write
24.0 26.0
258 N64:17 40817 High Superheat Start
Offset Temp
F-INT Read-
Write
4.0 6.0
Alarms/Trips
(Page 3)
259 N65:0 40830 Prelube Oil Pressure
Alarm
F-INT Read
260 N65:1 40831 Prelube Oil Pressure Trip F-INT Read
261 N65:2 40832 Run Oil Pressure Alarm F-INT Read
262 N65:3 40833 Run Oil Pressure Trip F-INT Read
263 N65:4 40834 High Filter Diff. Start
Press. Alarm
F-INT Read
264 N65:5 40835 High Filter Diff. Start
Press. Trip
F-INT Read