Service manual

B - 83
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B Vission 20/20 Application Procedures
189 N62:2 40642 Slide Valve Setpoint #1
Enabled
INT 0 = Disabled, 1 =
Enabled
Read
190 N62:3 40643 Slide Valve Setpoint #2
Enabled
INT 0 = Disabled, 1 =
Enabled
Read
191 N62:4 40644 Oil Pump Press. Restart
Ratio (ON)
F-INT Read
192 N62:5 40645 Oil Pump Press. Restart
Ratio (OFF)
F-INT Read
193 N62:6 40646 Oil Sep. Heater Temp. F-INT Read
194 N62:7 40647 Volume Slide Adjustment
%
INT Read
195 N62:8 40648 Soft Load % INT Read
196 N62:9 40649 Capacity Range Min % F-INT Read
197 N62:10 40650 Capacity Range Max % F-INT Read
198 N62:11 40651 Rate Deadband F-INT Read
199 N62:12 40652 Enable Load Anticipating
Algorithm
INT 0 = Disabled, 1 =
Enabled
Read
Compressor VFD
200 N70:0 40670 VFD Gain (P) INT Read
201 N70:1 40671 VFD Reset (I) INT Read
202 N70:2 40672 VFD Rate (D) INT Read
203 N70:3 40673 Step 1 VFD Minimum
Slide Position
INT Read
204 N70:4 40674 Step 1 VFD Maximum
Slide Position
INT Read
205 N70:5 40675 Step 1 VFD Minimum
Speed (rpm)
INT Read
206 N70:6 40676 Step 1 VFD Maximum
Speed (rpm)
INT Read
207 N70:7 40677 2 Step VFD Control
Enabled
INT 0 = Disabled, 1 =
Enabled
Read
208 N70:8 40678 Step 2 VFD Minimum
Slide Position
INT Read
209 N70:9 40679 Step 2 VFD Maximum
Slide Position
INT Read
210 N70:10 40680 Step 2 VFD Minimum
Speed (rpm)
INT Read
211 N70:11 40681 Step 2 VFD Maximum
Speed (rpm)
INT Read
Cool Compression
212 N71:0 40700 Auto Load Enabled INT 0 = Disabled, 1 =
Enabled
Read
213 N71:1 40701 Auto Load @ Start INT Read
214 N71:2 40702 Auto Load Timer (mins) F-INT Read