Appendix B • Vission 20/20 Application Procedures
167 N61:5 40615 Low Suct Press Force
Unload Setpoint #1
F-INT Read
168 N61:6 40616 High Motor Amps Stop
Load Setpoint #2
F-INT Read
169 N61:7 40617 High Motor Amps Force
Unload Setpoint #2
F-INT Read
170 N61:8 40618 High Disch Press Stop
Load Setpoint #2
F-INT Read
171 N61:9 40619 High Disch Press Force
Unload Setpoint #2
F-INT Read
172 N61:10 40620 Low Suct Press Stop Load
Setpoint #2
F-INT Read
173 N61:11 40621 Low Suct Press Force
Unload Setpoint #2
F-INT Read
174 N61:12 40622 Liquid Inj. Solenoid #1
Temp
F-INT Read
175 N61:13 40623 Liquid Inj. Solenoid #2
Temp
F-INT Read
176 N61:14 40624 Liquid Inj. Open % F-INT Read
177 N61:15 40625 Liquid Inj. Oil Sep. Temp.
Override
F-INT Read
178 N61:16 40626 Liquid Inj. Motorized
Valve Gain (P)
F-INT Read
179 N61:17 40627 Liquid Inj. Motorized
Valve Reset (I)
F-INT Read
180 N61:18 40628 Liquid Inj. Motorized
Valve Rate (D)
F-INT Read
181 N61:19 40629 Minimum Valve Open
Enabled
INT 0 = Disabled, 1 =
Enabled
Read
182 N61:20 40630 Avg. With Oil Manifold
Temperature
INT 0 = Disabled, 1 =
Enabled
Read
183 N61:21 40631 High Discharge
Superheat Stop Load
Setpoint #1
F-INT Read
184 N61:22 40632 High Discharge
Superheat Force Unload
Setpoint #1
F-INT Read
185 N61:23 40633 High Discharge
Superheat Stop Load
Setpoint #2
F-INT Read
186 N61:24 40634 High Discharge
Superheat Force Unload
Setpoint #2
F-INT Read
Misc 2
187 N62:0 40640 Slide Valve Setpoint #1 INT Read
188 N62:1 40641 Slide Valve Setpoint #2 INT Read