Service manual

B - 81
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B Vission 20/20 Application Procedures
148 N58:8 40578 Stop Delay Time Setpoint
#2
INT Read-
Write
0 300
149 N58:9 40579 Minimum Slide Position
Setpoint #2
INT Read-
Write
0 100
Pumpdown
150 N59:0 40590 Stop Pressure Setpoint #1 F-INT Read-
Write
-15.0 200.0
151 N59:1 40591 Stop Delay Time Setpoint
#1 (seconds)
INT Read-
Write
060
152 N59:2 40592 Minimum Slide Position
Setpoint #1
INT Read-
Write
050
153 N59:3 40593 Stop Pressure Setpoint #2 F-INT Read-
Write
-15.0 200.0
154 N59:4 40594 Stop Delay Time Setpoint
#2 (seconds)
INT Read-
Write
060
155 N59:5 40595 Minimum Slide Position
Setpoint #2
INT Read-
Write
050
156 N59:6 40596 Pumpdown Operation INT 0 = Stop, 1 = Start Read-
Write
Pulldown
157 N60:0 40600 Step Pressure F-INT Read-
Write
0.0 10.0
158 N60:1 40601 Delay Per Step (hours) F-INT Read-
Write
0.1 20.0
159 N60:2 40602 Stop Pressure F-INT Read-
Write
-15.0 200.0
160 N60:3 40603 Auto Cycle Differential F-INT Read-
Write
1.0 20.0
161 N60:4 40604 Initiate Pulldown at Next
Start
INT 0 = Disable, 1 =
Enable
Read-
Write
Misc 1
162 N61:0 40610 High Motor Amps Stop
Load Setpoint #1
F-INT Read
163 N61:1 40611 High Motor Amps Force
Unload Setpoint #1
F-INT Read
164 N61:2 40612 High Disch Press Stop
Load Setpoint #1
F-INT Read
165 N61:3 40613 High Disch Press Force
Unload Setpoint #1
F-INT Read
166 N61:4 40614 Low Suct Press Stop Load
Setpoint #1
F-INT Read