Service manual
B - 80
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B • Vission 20/20 Application Procedures
126 N57:4 40554 Cap Dec Proportional
Band Setpoint #1
F-INT Read-
Write
0.5 20.0
127 N57:5 40555 Setpoint #2 (Pressure,
Temp)
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)
128 N57:6 40556 Cap Inc Time Interval
Setpoint #2
F-INT Read-
Write
0.5 5.5
129 N57:7 40557 Cap Inc Proportional
Band Setpoint #2
F-INT Read-
Write
0.5 20.0
130 N57:8 40558 Cap Dec Time Interval
Setpoint #2
F-INT Read-
Write
0.5 5.5
131 N57:9 40559 Cap Dec Proportional
Band Setpoint #2
F-INT Read-
Write
0.5 20.0
132 N57:10 40560 Cap Inc Pulse Time
Setpoint #1
F-INT Read-
Write
0.5 5.5
133 N57:11 40561 Cap Inc Dead Band
Setpoint #1
F-INT Read-
Write
1.0 50.0
134 N57:12 40562 Cap Dec Pulse Time
Setpoint #1
F-INT Read-
Write
0.5 5.5
135 N57:13 40563 Cap Dec Dead Band
Setpoint #1
F-INT Read-
Write
1.0 50.0
136 N57:14 40564 Cap Inc Pulse Time
Setpoint #2
F-INT Read-
Write
0.5 5.5
137 N57:15 40565 Cap Inc Dead Band
Setpoint #2
F-INT Read-
Write
1.0 50.0
138 N57:16 40566 Cap Dec Pulse Time
Setpoint #2
F-INT Read-
Write
0.5 5.5
139 N57:17 40567 Cap Dec Dead Band
Setpoint #2
F-INT Read-
Write
1.0 50.0
Auto Cycle
140 N58:0 40570 Start (Press/Temp)
Setpoint #1
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)
141 N58:1 40571 Start Delay Time Setpoint
#1
INT Read-
Write
0 300
142 N58:2 40572 Stop (Press/Temp)
Setpoint #1
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)
143 N58:3 40573 Stop Delay Time Setpoint
#1
INT Read-
Write
0 300
144 N58:4 40574 Minimum Slide Position
Setpoint #1
INT Read-
Write
0 100
145 N58:5 40575 Start (Press/Temp)
Setpoint #2
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)
146 N58:6 40576 Start Delay Time Setpoint
#2
INT Read-
Write
0 300
147 N58:7 40577 Stop (Press/Temp)
Setpoint #2
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)