Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B • Vission 20/20 Application Procedures
112 N56:4 40504 Remote Pulse Load F-INT "0 = Stop Pulse
10 = 1 Second Pulse
15 = 1.5 Second
Pulse
20 = 2 Second Pulse
…
145 = 14.5 Second
Pulse
150 = 15 Second
Pulse"
Read-
Write
113 N56:5 40505 Remote Pulse Unload F-INT "0 = Stop Pulse
10 = 1 Second Pulse
15 = 1.5 Second
Pulse
20 = 2 Second Pulse
...
145 = 14.5 Second
Pulse
150 = 15 Second
Pulse"
Read-
Write
114 N56:6 40506 Capacity Hold % INT 0 – 100 Read-
Write
115 N56:7 40507 Active Setpoint ENUM "1 = Setpoint 1
2 = Setpoint 2 (if
enabled)"
Read-
Write
116 N56:8 40508 Start Command INT 1 = Start Read-
Write
(See
Notes)
117 N56:9 40509 Stop Command INT 1 = Stop Read-
Write
118 N56:10 40510 Auto-Cycle Enable/
Disable
INT 0 = Disable, 1 =
Enable
Read-
Write
119 N56:11 40511 Pumpdown Enable/
Disable
INT 0 = Disable, 1 =
Enable
Read-
Write
120 N56:12 40512 Pulldown Enable/Disable INT 0 = Disable, 1 =
Enable
Read-
Write
N56:13 40513 Force to local control INT 1 = To local Read-
Write
Compressor Control
Setpoints
122 N57:0 40550 Setpoint #1 (Pressure,
Temp)
F-INT Read-
Write
(-15.0,
-100.0)
(200.0,
150.0)
123 N57:1 40551 Cap Inc Time Interval
Setpoint #1
F-INT Read-
Write
0.5 5.5
124 N57:2 40552 Cap Inc Proportional
Band Setpoint #1
F-INT Read-
Write
0.5 20.0
125 N57:3 40553 Cap Dec Time Interval
Setpoint #1
F-INT Read-
Write
0.5 5.5