Appendix B Vission 20/20 Application Procedures
104 N55:15 40415 Refrigerant ENUM "0 = R11
1 = R12
2 = R13
3 = R22
4 = R113
5 = R114
6 = R134a
7 = R290 - Propane
8 = R404a
9 = R500
10 = R502
11 = R503
12 = R507
13 = R717
14 = R717 - Cool
Comp
15 = R744 - CO2
16 = R771
17 = R1270 -
Propylene
18 = Natural Gas
19 = Other"
Read
105 N55:16 40416 Runtime Hours (x1000) INT Read
106 N55:17 40417 Runtime Hours (1-999) INT Read
107 N55:18 40418 Remote Lock Mode INT 0 = OFF, 1 = ON Read
Commands
108 N56:0 40500 Alarm Reset INT 1 = Perform Reset Read-
Write
109 N56:1 40501 Active Remote Control ENUM "0 = None (Local)
1 = Direct I/O
2 = Serial
3 = Ethernet"
Read-
Write
110 N56:2 40502 Remote Capacity Control
Select
ENUM "0 = Auto Capacity
Control
1 = Pulse Load /
Unload
2 = Hold Capacity %"
Read-
Write
111 N56:3 40503 Auto Capacity Control
Type
ENUM "0 = Suction Pressure
(if enabled)
1 = Process
Temperature (if
enabled)
2 = Discharge
Pressure (if enabled)"
Read-
Write