Service manual

B - 77
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B Vission 20/20 Application Procedures
99 N55:10 40410 Current Run Mode ENUM 0 = Idle
1 = Waiting
2 = Starting
3 = Manual
4 = Auto (Internal
Capacity Control)
5 = Remote Auto
(Internal Capacity
Control)
6 = Remote Load/
Unload
7 = Remote Capacity
Hold %
8 = Remote Ready
(Idle)
9 = Direct I/O Auto
Capacity
10 = Direct I/O
Manual Capacity
11 = Direct I/O
Capacity Hold %
12 = Auto
Sequencing
Read
100 N55:11 40411 Load Limiting Condition WORD "Bit 0 = High Motor
Amps
Bit 1 = High
Discharge Pressure
Bit 2 = Low Suction
Pressure
Bit 3 = High
Discharge
Superheat"
Read
101 N55:12 40412 Oil Pump Status INT 0 = OFF, 1 = ON Read
102 N55:13 40413 Oil Pump Operation ENUM "0 = None
1 = Cycling
2 = Full Time
3 = Cool
Compression"
Read
103 N55:14 40414 Compressor Model ENUM "0 = VSR
1 = VSM
2 = VSS
3 = VRS"
Read