Service manual
B - 75
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B • Vission 20/20 Application Procedures
53 N52:13 40113 Chiller Inlet Temperature F-INT Read
54 N52:14 40114 Condenser Pressure F-INT Read
55 N52:15 40115 Remote Setpoint F-INT Read
56 N52:16 40116 Auxiliary 1 F-INT Read
57 N52:17 40117 Auxiliary 2 F-INT Read
58 N52:18 40118 Auxiliary 3 F-INT Read
59 N52:19 40119 Auxiliary 4 F-INT Read
60 N52:20 40120 Auxiliary 5 F-INT Read
61 N52:21 40121 Auxiliary 6 F-INT Read
62 N52:22 40122 Auxiliary 7 F-INT Read
63 N52:23 40123 Auxiliary 8 F-INT Read
64 N52:24 40124 Auxiliary 9 F-INT Read
65 N52:25 40125 Auxiliary 10 F-INT Read
66 N52:26 40126 Auxiliary 11 F-INT Read
67 N52:27 40127 Auxiliary 12 F-INT Read
68 N52:28 40128 Auxiliary 13 F-INT Read
69 N52:29 40129 Auxiliary 14 F-INT Read
70 N52:30 40130 Auxiliary 15 F-INT Read
71 N52:31 40131 Auxiliary 16 F-INT Read
Analog Outputs
72 N53:0 40200 Compressor VFD (mA) F-INT Read
73 N53:1 40201 Condenser VFD F-INT Read
74 N53:2 40202 Slide Valve Output F-INT Read
75 N53:3 40203 Liquid Injection
Motorized Valve
F-INT Read
76 N53:4 40204 Profi le VFD F-INT Read
77 N53:5 40205 Spare #1 F-INT Read-
Write
(See
Notes)
4.0 20.0
78 N53:6 40206 Spare #2 F-INT Read-
Write
(See
Notes)
4.0 20.0
79 N53:7 40207 Spare #3 F-INT Read-
Write
(See
Notes)
4.0 20.0
Calculated Values
80 N54:0 40250 Filter Differential Pressure F-INT Read
81 N54:1 40251 Start Oil Pressure F-INT Read
82 N54:2 40252 Run Oil Pressure F-INT Read