Appendix B Vission 20/20 Application Procedures
Pulldown OPERATION EXAMPLE
Assumptions:
Compressor is off
Pulldown is selected
“Initiate Pulldown at Next Start” is selected
Current suction pressure = 80 PSIG
Auto-cycle setpoints are enabled
Pulldown setpoints are setup per the Setpoint Selection Example
Variables:
Step Pressure = 5.0 PSIG
Delay Per Step = 20 hours
Stop Pressure = 20 PSIG
Auto-cycle Differential = 4 PSIG
Operator presses Unit Start Auto button and the compressor starts. Two items occur:
The Pulldown feature is now operational
When Pulldown feature is active:
Pumpdown is disabled (Pulldown and Pumpdown operation modes are mutually exclusive)
Low Suction Pressure Stop Load and Unload setpoints are active (Make sure that these setpoints do not
con ict with the Pulldown Stop setpoint)
The Pulldown setpoints are immediately calculated:
Initial Pulldown setpoint = Current Suction Pressure 80 psig minus Step Pressure (5 psig) = 75 psig
Auto-Cycle Start Pressure = Pulldown setpoint (75 psig) plus Auto-Cycle Differential (4 psig) = 79 psig
Auto-cycle Stop Pressure = Pulldown setpoint (75 psig) minus Auto-Cycle Differential (4 psig) = 71 psig
The compressor will maintain the suction pressure at 75 psig for the rst 20 hours, and then the next calculation of
Pulldown setpoints will be calculated:
Subsequent Pulldown setpoint = Suction Pressure setpoint (75 psig) minus Step Pressure (5 psig) = 70 psig.
Auto-Cycle Start Pressure = Pulldown Setpoint (70psig) plus Auto-Cycle Differential (4 psig) = 74 psig
Auto-Cycle Stop Pressure = Pulldown Setpoint (70 psig) minus Auto-Cycle Differential (4 psig) = 66 psig
After 20 hours of running at 70 psig, the next set of Pulldown setpoints are calculated. This is repeated until the target
setpoint (Stop Pressure setpoint) is reached. The Pulldown operation is then disabled and the compressor will con-
tinue to operate at this setpoint.