Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Section 24 Twin Screw Control
Figure 24-3. Slide Calibration - Twin Screw Bump Pop-Up Window
Limit” setpoint to de ne an area within the mechani-
cal stops for normal slide travel. These software limits
purpose is to prevent the slide from actually hitting
the mechanical stops which could result in a number
of undesirable consequences. By default, the soft-
ware limits are set to 150mV from either end point.
The position percentage is calculated from the soft-
ware limits. Therefore, it is possible to read a value
greater than 100% or less than 0% if inertial carries
the slides after these limits are reached.
Position Signal Type:
• Position signals can be 0-5 VDC or 4-20mA to indi-
cate current slide valve position.
Compressor Bump Pop-Up Window
This window allows the operator to bump the com-
pressor to ush out any oil in the compressor after a
slide valve calibration, see Figure 24-3. If the oil level
is below the lowest sight glass in the oil separator,
then bumping the compressor is recommended.