Service manual

8 – 3
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9
for a time period that exceeds the setpoint of the
Accumulative Anti-Recycle Timer, then when the
compressor shuts down, it will be allowed to restart
immediately.
Compressor Interlock Bypass:
Once the Vission 20/20 has sent a command to the
compressor starter to start, a return signal is expect-
ed. This timer de nes how much time to wait for that
signal before setting a trip condition.
High Motor Amps Safety Bypass:
Starting motors can typically pull much more than
its rates full load amps for a short time. This timer ig-
nores that sudden inrush of current for the speci ed
time.
Emergency Stop Timer:
• De nes the amount of time the compressor is in a
False start condition before activating the Emergency
stop. The emergency stop output can be connected
to a shunt-trip in the case of a run away compressor
to remove all power to the system.
Low Suction Pressure Safety Bypass:
Sets the time that the compressor is allowed to run
at lower suction pressure then would usually be allow
at start-up.
High Superheat Temp Safety Changeover:
This timer activates at shutdown and changes the re-
start parameters if the time has not been met.
Section 8 Timers
Figure 8-2. Timers Screen - Page 2