Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9
Auto Cycle Differential:
This setpoint de nes the offset pressure values for
Auto Cycle Start Pressure and Stop Pressure from the
Suction Pressure setpoint. Auto Cycle Start Pressure
setpoint will be Suction Pressure setpoint increment-
ed by this setpoint pressure value, while Auto Cycle
Stop Pressure value will be Suction Pressure setpoint
decremented by this setpoint pressure value.
When Pulldown feature is enabled, Pumpdown checkbox
is automatically grayed out. Similarly when Pumpdown
feature is enabled, Pulldown checkbox is automatically
grayed out and hence, the user will not be able to op-
erate Pulldown feature. This is done to keep Pulldown &
Pumpdown features mutually exclusive.
Control Mode
This drop down box gives the operator the ability to
change the type of control mode such as suction pres-
sure control or process temperature control. The
operator can also switch from setpoint 1 and setpoint 2
for each control method. What is available in this drop-
down box is dependent on the number and type of con-
trol selected in the con guration screen, see Figure 6-8.
Compress Control Screen - Misc 1 (Control Mode).
Stop Load and Force Unload
The stop load and force unload feature’s primary pur-
pose is to attempt to prevent the compressor from
tripping off due to particular instrument reading. For
example, if the suction pressure drops too low, the com-
pressor will trip off for safety reasons. However, the stop
load & force unload algorithm recognizes a potential trip
and either stops the compressor from loading up or even
unloads the compressor to prevent the trip.
Stop load:
When this value is reached, the capacity slide will not
Section 6 Compressor Control
Figure 6-8. Compressor Control Screen - Misc. 1 (Control Mode)