Variable Frequency Drive (VFD) Settings
Control
The VFD page is where the operator can tune the motor
VFD for desired operation, see Figure 6-4. Compressor
Control Screen - VFD Settings Control. A Vilter compres-
sor uses the variable speed of a VFD controlled motor to
vary the amount of work or capacity of the compressor.
The basic one step VFD control will use the capacity slide
to control the fi rst half of the total available capacity and
the motor speed to control the second half of the total
available capacity, see Figure 6-5. VFD One-Step Control
Method. For example, if the compressor needs to load
to 100% of its capacity. The control algorithm will fi rst
move the capacity slide to its maximum position, then
the motor speed will ramp up to its maximum speed.
In the unloading direction, the motor speed will ramp
down to its minimum speed, then the capacity slide will
move to its minimum position.
The two-step control method works much like the one-
step method but divides the control into four sections,
see Figure 6-6. VFD Two-Step Control Method. While
loading; the compressor will fi rst move the capacity
slide to the maximum set for step one then speed up the
motor to its maximum speed for the same step. Once
step one has completed, the control algorithm will again
move the capacity slide to the maximum position and
the maximum speed of step two. At this point the com-
pressor would be fully loaded. Unloading occurs in the
reverse direction. The two-step control method is not
typical for most installations and is normally used when
a Vilter engineer recommends it.NOTE
VFD installation is not covered in this manual. A VFD
that is not properly installed and confi gured has the
potential of causing intermittent and dangerous
problems. Please consult your VFD manual.
1 Step VFD Control:
• Enables the fi rst step in the VFD control algorithm.
This check box is not deselectable by the operator.
Capacity Slide Position:
Section 6 • Compressor Control
Figure 6-4. Compressor Control Screen - VFD Settings Control