Service manual

25 – 2
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9
enable Superheat Monitoring on the screen.
As previously described, Cool Compression
compressor does not have an oil pump. Instead
it has a suction oil injection solenoid to pro-
vide oil and liquid ammonia for lubrication and
cooling.
Cool Compression liquid injection 1 and liq-
uid injection 2 outputs will operate as high / low
pressure ratio solenoid outputs.
Control Functions
In the Compressor Control Menu, special cool compres-
sion control functions are now available, see Figure 25-2.
Compressor Control Screen - Cool Compression Control
(Page 4). These new functions are:
• Auto Load
Suction Oil Injection Settings
Danfoss Positioning Valve Settings
Auto Load
Auto load operation will force the compressor to
load to a minimum value once the compressor has
started. By loading the compressor to a minimum
value, and maintaining this capacity, a pressure ratio
is created across the compressor, to ensure adequate
lubrication of the compressor, and also that the com-
pressor does not experience high discharge super-
heat conditions. Since compressor lubrication is of
great importance, all load limiting is disabled when
auto load is engaged.
Auto Load at Start
• De nes the value at which Compressor (ca-
pacity slide) should be loaded (and maintained)
at start if Auto Load is enabled.
Auto Load Timer
• This timer de nes the maximum time that
the Auto Load operation will be engaged. After
the timer expires, Auto Load will be disengaged.
Section 25 Cool Compression Control
Figure 25-2. Compressor Control Screen - Cool Compression Control (Page 4)