Technical data
Instructions Manual cod. 1592001120
1592001121 Universal-R3 GB 19.11.2004.doc
rel. 1.0
Pa. 7 / 15
UNIVERSAL R
Label
Adjustment Range
Factory defaults with parameter “tC” 1- 6
Thermostat probe calibration
Ot
- 12.0
÷
12.0
°
c
0.0
0.0
0.0
0.0
0.0
0.0
Evaporator probe calibration
OE
- 12.0
÷
12.0
°
c
0.0
0.0
Display Resolution
rES
0 = With decimal point
1 = No decimal point
0
0
0
0
0
0
Temperature measurement unit (°C/°F)
CF
0 =
°
Celsius
1 =
°
Fahrenheit
0
0
0
0
0
0
Compressor ON time with faulty probe
COn
0
÷
250 mins.
15
15
15
15
15
15
Compressor OFF time with faulty probe
COF
0
÷
250 mins.
30
30
30
30
30
30
Alarm muting configuration for
buzzer & relay
tbA
0 = Mute buzzer only
1 = Mute buzzer & relay
1
1
1
1
1
1
Digital input configuration
dic
0=Start defrost: 1=Door switch
2=Auxiliary relay: 3=Energy saving
4=Remote On/OFF:
5=Generic alarm: 6=Serious alarm
5
5
5
5
5
5
Digital input polarity
diP
0=Closed circuit: 1=Open circuit
0
0
0
0
0
0
Digital input delay
did
0-255 minutes
0
0
0
0
0
0
Door open – compressor / fan status
odc
0=No change: 1=Fan off
2=Compressor off:
3=Compressor & Fan off
0
0
0
0
0
0
Configure the 4
th
relay
oAc
0=Alarm relay:
1= Heater relay (for Neutral Zone)
2=Auxiliary relay
0
0
0
0
0
0
Alarm relay polarity
AoP
0 = 13-14 closed with alarm
1 = 13-14 open with alarm
0
0
0
0
0
0
Door open alarm delay
doA
0-250 minutes
15
15
15
15
15
15
Exclude temperature alarm - door open
dot
0-250 minutes
20
20
20
20
20
20
Restart regulation with door open alarm
rrd
0=No: 1=Yes
0
0
0
0
0
0
Temperature deviation from normal
Set Point during Energy Saving
HES
-30°C / +30°C
0
0
0
0
0
0
Parameter table
Ptb
For factory use only
-
-
-
-
-
-
Software release number
rEL
Read only
-
-
-
-
-
-
Evaporator probe temperature
Prd
Read only
-
-
-
-
-
-
READ ON IF YOU NEED MORE DETAIL
7.
SERVICE REPLACEMENT - MODELS AND PROBE INFORMATION
The Dixell Universal-R can directly replace all the following controllers for their most typical applications as well as many
others not listed. It is compatible with the existing PTC or NTC sensors from most other leading brands. If the existing
sensors are incompatible or possibly faulty, they can be replaced by the two new NTC sensors which come supplied
with the Universal-R. (When ever practical, replacement of the sensors is always recommended as good practise. )
LAE
MTR11/T1RDS MTR11/T1RES SDU11/T1RES SDU11/T1REBS SDU112
MCDU11/T1RDS MCDU11/T1RDS/1 MCDU11/T1RDS/2 MCDU11/T1RDS/3 CDC112/T1R2S
CDC112/T1RES CDC112/T1RBS SDU12/T0RES SDU12/T0REB SDU12/T0RD
SDU12T0RDC LDU151E LDU152E CDC112/T1R2 CDC112/T1R3B
Carel
IR32S IR32Y IR32C CR32S CR32T
CR32X CR32Y PJ32Y PJ32S PJ32X
PJ32C