Installation






For units provided with a ground connection, a green (with or without one or
more yellow stripes) insulated grounding conductor identical in size, insulation
material, and thickness to the grounded and ungrounded conductors must be
installed (ref. NEC Table 250-95) and referenced back to an acceptable building
earth ground.
Attachment plugs, receptacles, etc. in the vicinity of the STFE Elite Series must
be of grounding type, with the grounding conductors connected to an acceptable
building earth ground.
Terminals, lugs, and connectors used in installation must be suitable for the
material of the conductors. Conductors of dissimilar metals shall not be inter-
mixed in a terminal or splicing.
