Brochure
24
Data/signal line surge protection
STC-DRS SERIES
CATALOG
NUMBER
MAX PEAK
SIGNAL VOLTAGE
NOMINAL
BREAKDOWN
VOLTAGE
MAX CURRENT
1P 10X1000 MS
(OCCURRENCES)
PEAK CURRENT
8X20 MS
TYP. CAP
(PF)
MAX.
CONTINUOUS
CURRENT
NOMINAL
SERIES
RESISTANCE
STC-DRS-232
15 22 >100 10KA 1500 150ma 5 Ω
STC-DRS-036
30 36 >100 10KA 1500 150ma 5 Ω
STC-DRS-060
52 60 >100 10KA 1500 150ma 5 Ω
Notes:
ese protectors are intended for indoor use on communication loop
circuits that have been isolated from the Public Switch Telephone Network.
e communication loop circuits shall not be exposed to accidental contact with
the electric light or power conductors. e protectors shall be installed per the
applicable requirements of the National Electric Code, ANSI/NFPA 70.
Using three-stage hybrid technology, this DIN Rail
mountable, single pair, surge suppressor attenuates
over-voltage transients with gas tubes and silicon
avalanche components while resetable fuses (PTCs)
mitigate sneak currents. e PTC increases resistance
by several orders of magnitude when over-currents
exceed safe levels. A normal state resumes when over-
currents are removed. e ability to self-restore in this
manner signicantly increases suppressor performance
and survivability.
e STC-DRS Series mounts onto a standard 35 mm
industrial DIN rail. ere are three Field Side and three
Electronics Side screw terminals. One is reserved for
a shield. ree electrically tied ground terminals are
provided for grounding the unit to building-approved
ground. e shield is isolated from ground.
Features
• Low-Voltage data surge protection
• ree-Stage hybrid technology
• Sneak/Fault current protection with
resetable fuses (PTCs)
• Low prole packaging
• Easy installation
• Fits standard 35 mm DIN Rail
• Fast response time <1 nanosecond
• Five year limited warranty
Selection Table
Dimensions