Brochure
21
active tracking filtering with surge PrOtectiOn
STFE ELITE SERIES
Specications
Connection Diagram
DESCRIPTION
STFEXXX-10N STFEXXX-24L
Input Voltage 120 V (0-150 Vrms) 240 V (0-275 Vrms)
Line Frequency 47 - 63 Hz
Response Time < .5 ns normal mode, <5 ns common mode
Enclosure Fully Enclosed Metal Housing
Fusing Reference Fuse/Circuit Breaker Chart
Status Indication Green LED “OK”/Form C Contact/10 Amps @ 250 Vac or 5 Amps @ 100 Vdc
Connection/Mounting Type DIN Rail Mount
Operating Temperature -40°C to +50°C at full load Derate Linearly to 60% at +70ºC
Weight - lbs (kg) 1.7 lbs (0.70 kg)
Dimensions - in (mm)
(H x W x D)
4.88 x 2.56 x 4.56
(124.0 x 65.0 x 116.0)
Operating Humidity 0% to 95% Non-condensing
Peak Surge Current Capability
Per Phase 30,000 Amps
Line to Neutral 20,000 Amps
Line to Ground 10,000 Amps
Neutral to Ground 10,000 Amps
Load Surge Current Rating
10m Sec 5 x Nominal
1 sec 3 x Nominal
10 sec 2 x Nominal
Frequency Response
Normal Mode (Forward-Reverse) 100 kHz to 50 MHz 90 dB Max
Common Mode (Forward-Reverse) 5 MHz to 50 MHz 60 dB Max
Transient Reduction
(IEEE C62.41)
Typical Category A Ringwave
(6 kV, 200A, 100 kHz)
< 60 V Peak
Typical Category B Ringwave
(6 kV, 500A, 100 kHz)
<100 V Peak UL 1449
Warranty 5 year limited warranty
To load or
equipment
protect
Relay
Contacts
L/L1
L/L1
L/L1
L/L1
LOAD
LINE
Line input
from source
N/L2
N/L2
N/L2
N/L2
GND
COMNO NC
GND
GND
GND
To remote indication
if needed