Instruction manual
MODEL 5081-C SECTION 7.0
PROGRAMMING
7.2.3 Procedure
1. Press PRo G on the remote controller. The OutPut submenu appears.
2. Press ENTER. The screen displays the 4 MA prompt. u se the arrow keys to change
the setting. Press ENTER to save.
3. The screen displays the 20 MA prompt. u se the arrow keys to change the setting.
Press ENTER to save.
4. The screen displays the HoLd prompt. u se the arrow keys to change the setting to
the output desired when the transmitter is in hold. The range is 3.80 to 22.00 mA.
Entering 00.00 causes the transmitter to hold the output at the value it was when
placed in hold. The hold setting overrides the fault setting. Press ENTER to save.
5. The screen displays the FAULt prompt. u se the arrow keys to change the setting to
the output desired when the transmitter detects a fault. The range is 3.80 to 22.00 mA.
Entering 00.00 causes the transmitter to hold the output at the value it was when the
fault occurred. Press ENTER to save.
6. The screen displays the dPn prompt. u se the arrow keys to change the setting. The
range is 0 to 255. Press ENTER to save.
7. The screen displays the tESt prompt. u se the arrow keys to enter the desired test cur-
rent. Press ENTER to start the test. Press EXiT to end the test.
8. Press RESET to return to the process display.