Instruction manual

6
MODEL 5081-C SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
1.7 FOUNDATION FIELDBUS
Figure 1-4 shows a 5081-C-FF being used to measure conductivity. The figure also shows three ways in which Fieldbus
communication can be used to read process variables and configure the transmitter.
FIGURE 1-4. CONFIGURING MODEL 5081-C TRANSMITTER w ITH FOUNDATION FIELDBUS
1.8 GENERAL SPECIFICATIONS
Model: 5081-C-FF Fieldbus Transmitter
Type: Contacting Conductivity Transmitter
Device ITK Profile: 6 (Released for iTK 6.0.0 / 6.0.1)
Manufacturer Identification (MANUFAC_ID): 0x524149
Device Type (DEv _TyPE): 0x4084
Device Revision (DEv_REv): 0x03
Linkmaster: Yes
Number of Link Objects: 20
vCR’s supported: 20
Mandatory Features:
Resource Block
Alarm and Events
Function Block Linking
• Trending
Multi-Bit Alert Reporting
Field d iagnostics
Additional Features:
Common Software d ownload
Block instantiation
Supports d eltaV Auto Commissioning
Supports d eltaV Auto Replacement
Supports d eltaV Firmware Live d ownload
PlantWeb Alerts with re-annunciation / multibit
Supports Easy Configuration Assistant
Function Blocks (Execution Time):
4 – Analog input Blocks (15 mseconds)
Ai Block Channels:
Channel 1: Conductivity, Resistivity, Concentration
Channel 2: Temperature
Channel 3: Raw Conductivity
Proportional integral d erivative (25 mseconds)
Power:
• Two Wire d evice; Fieldbus Polarity insensitive
Current d raw: 21 mA
d evice Certifications: iS / FiSCo
Maximum certified input Voltage for iS: 30V
Maximum certified input current for iS: 300mA
Maximum certified input power for iS: 1.3W
internal Capacitance (Ci): 0 nF
internal inductance (Li): 0 μH