Instruction manual

39
FIGURE 4-20. FM Intrinsically Safe Installation (1 of 2) for Model Xmt-P-FI
10/6/04
10/6/04 10/6/04
14. METAL CONDUIT IS NOT REQUIRED BUT IF USED BONDING
BETWEEN CONDUIT IS NOT AUTOMATIC AND MUST BE
PROVIDED AS PART OF THE INSTALLATION.
Isc, It OR Io;
Voc, Vt OR Uo;
Po;
COMPONENT THAT DOES NOT DISSIPATE MORE THAN 1.3W.
AND THE NEC, ANSI/NFPA 70. THEY CAN NOT GENERATE NOR STORE MORE THAN 1.5V, 100mA, 25mW OR A PASSIVE
6. SENSORS WITHOUT PREAMPS SHALL MEET THE REQUIREM
ENTS OF SIMPLE APPARATUS AS DEFINED IN ANSI/ISA RP12.6
OR SIMPLE APPARATUS
FM APPROVED DEVICE
+PH SENSOR
3. INTRINSICALLY SAFE APPARATUS (MODEL XMT-P-FI, MODEL 375)
Pmax NOT GREATER THAN 0.9 W
Isc OR It NOT GREATER THAN 200 mA
Voc OR Vt NOT GREATER THAN 30 V
SUPPLY/SIGNAL TERMINALS TB2-1, 2 AND 3.
1. ANY SINGLE SHUNT ZENER DIODE SAFETY BARRIER APPRO
VED BY FM HAVING THE FOLLOWING OUTPUT PARAMETERS:
4. PREAMPLIFIER TYPE 23546-00, 23538-00 OR 23561-00 MAY BE UTILIZED INSTEAD OF THE MODEL XMT-P-FI
MAY BE ALS
O USED. THE OUTPUT PARAMETERS SPECIFIED IN TABLE II ARE VALID FOR EITHER PREAMPLIFIER.
2. THE MODEL XMT-P-FI TRANSMIT
TER INCLUDES INTEGRAL PREAMPLIFIER CIRCUITRY. AN EXTERNAL PREAMPLIFIER
XMTR
XMT-P-FI
MODEL
XMT-P-FI
XMT-P-FI ENTITY PARAMETERS
(FM APPROVALS)
MOD XMT-P-FI XMTR
0.0
SUPPLY / SIGNAL TERMINALS TB2-1, 2 AND 3
3 2 1
2 3 456 78 9 10 11 121
SPECIFIED IN TABLE I
THE CAPACITANCE AND INDUCTANCE OF THE LOAD CONNECTED TO THE SENSOR TERMINALS MUST NOT EXCEED THE VALUES
La Li (SENSOR) + Lcable.
WHERE Ca Ci (SENSOR) + Ccable;
23546-00 REMOTE PREAMPLIFIER.
TRANSMITTER INTEGRAL PREAMPLIFIER CIRCUITRY. A WEATHER RESISTANT ENCLOSURE MUST HOUSE THE TYP
E
(SEE NOTES 1 & 9)
SAFETY BARRIER
Li+ Lcable.
Ci+ Ccable;
Pmax OR Pi
Imax OR Ii
Vmax OR Ui
FIELD DEVICE INPUT ASSOCIATED APPARATUS OUTPUT
WITH ASSOCIATED APPARATUS WHEN THE FOLLOWING IS TRUE:
9. THE INTRINSICALLY SAFE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALL
Y SAFE DEVICES
380
17.5
La, Lt OR Lo
Ca, Ct OR Co
SYSTEMS FOR HAZARDOUS (CLASSIFIED) LOCATIONS" AND THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70) SECTIONS 504 AND 505.
5. INSTALLATION SHOULD BE IN ACCORDANCE WITH ANSI/ISA RP12.06.01 "INSTALLATION OF INTRINSICALL
Y SAFE
0.4
TABLE III
MODEL NO.
0
5.32
Vmax (Vdc)Li (mH)
Ci (nF)
Pmax (W)
Imax (mA)
0.0
321.9
ENTITY PARAMETERS: REMOTE TRANSMITTER INTERFACE
Isc max OUT:uA
Voc max OUT: Vdc
Pamx IN: W
Imax IN:mA
Vmax IN: Vdc
375
MODEL NO.
1.0
20030
Li (mH)
Ci (uF)
WHEN INSTALLING THIS EQUIPMENT.
10. ASSOCIATED APPARATUS MANUFACTURER'S INSTALLATION DRAWING MUST BE FOLLOWED
FM APPROVAL.
13. NO REVISION TO DRAWING WITHOUT PRIOR
FIELD COMMUNICATOR
ROSEMOUNT MODEL 375
TABLE III)
(SEE NOTE 3 AND
CLASS I AREA ONLY
INTERFACE FOR USE IN
REMOTE TRANSMITTER
SUITABILITY FOR DIVISION 2.
SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY OR
DISCONNECT POWER BEFORE SERVICING.
TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOS
PHERES,
GROUPS A, B, C, D, E, F, G;
DIVISION 1,
IS CLASS I, II, III,
HAZARDOUS AREA
WARNING-
INDUCTANCE (La) WHICH CAN BE SAFELY CONNECTED TO THE APPARATUS. (REF. TABLES I, II AND III).
INCLUDING INTERCONNECTING WIRING, MUST BE EQUAL OR LE
SS THAN THE CAPACITANCE (Ca) AND
UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF THE INTRINSICALLY SAFE APPARATUS,
DELIVERED BY THE ASSOCIATED APPARATUS (SAFETY BARRIER). IN ADDITION, THE MAXIMUM
EQUAL TO OR GREATER THAN THE VOLTAGE (Voc OR Vt) AND CURRENT (Isc OR It) WHICH CAN BE
THE VOLTAGE (Vmax) AND CURRENT (Imax) OF THE INTRINSICALLY SAFE APPARATUS MUST BE
AND ASSOCIATED APPARATUS (SAFETY BARRIER) SHALL ME
ET THE FOLLOWING REQUIREMENTS:
17.5 VDC MAX
POWER SUPP LY
UNSPECIFIED
12. THE ASSOCIATED APPARATUS MUST BE FM APPROVED.
8. RESISTANCE BETW
EEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1.0 Ohm.
7. DUST-TIGHT CONDUIT SEAL MUST BE USED WHEN INSTALLED IN CLASS II
AND CLASS III ENVIRONMENTS.
WARNING-
NON-HAZARDOUS AREA
LOAD
MORE THAN 250 Vrms OR Vdc.
11. CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE
J. FLO CK
B. JOHNSON
THIS DOCUMENT IS
CERTIFIED BY
REV
REV
REV
REV
REV
REV
REVISIONS NOT PERMITTED
W/O AGEN CY APPROVAL
SCHEMATIC, INSTALLATION
Uniloc
9/15/04
NOMINAL SURFACE FINISH 125
A
9064
10-6-04
1400300
2
1
SHEET OF
NONE
J. FLO CK
A
1400300
D
C
D
C
B
A
1
2
3
4
5
6
7
8
6
7
8
5
4
3
2
B
A
10-96
1
D
APPROVALS
.030
.XX
.XXX
.010
+
-
ANGLES
+
1/2
-
+
-
TOLERANCES
SOLID EDGE
CHK
REVISION
DATE
BYDESCRIPTION
ECO
LTR
NOTES: UNLESS OTHERWISE SPECIFIED
REVECO NO.
RELEASE DATE
PART NO.
ITEM
QTY
BILL OF MATERIAL
DESCRIPTION
DATE
THIS DWG CONVERTED TO
DRAWN
CHECKED
to those who may compete with Rosemount Analytical.
Rosemount Analytical, and is not to be made available
This document contains information proprietary to
TYPE
SCALE
TITLE
REV
DWG NO.
SIZE
ENGR APVD
PROJECT
MATERIAL
FINISH
MACHINED FILLET RADII .020 MAX
REMOVE BURRS & SHARP EDGES .020 MAX
DIMENSIONS ARE I N INCHES
UNLESS OTHERWISE SPECIFIED
Rosemount Analytical,
Uniloc Division
2400 Barranca Pkwy
Irvine , CA 92606
21.69
5.99
0.9645
29.97
7.97
64.15mA
13.03V
208.96mW
TB1-1 THRU 12
MODEL XMT-P-FI
GROUPS
GAS
OUTPUT PARAMETERS
(mH)
La
(uF)
Ca
C
D
TABLE I
59.97
A, B
Po
TABLE II
Uo
Io
PARAMETERS
OUTPUT
FM A