Instruction manual
2
MODEL XMT-P pH/ORP SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
1.2 SPECIFICATIONS
1.2.1 GENERAL SPECIFICATIONS
Case:
ABS (panel mount), polycarbonate (pipe/wall mount);
NEMA 4X/CSA 4 (IP65)
Dimensions
Panel (code -10): 6.10 x 6.10 x 3.72 in. (155 x 155 x
94.5 mm)
Surface/Pipe (code -11): 6.23 x 6.23 x 3.23 in. (158
x 158 x 82 mm); see page 15 for dimensions of pipe
mounting bracket.
Conduit openings: Accepts PG13.5 or 1/2 in. conduit fit-
tings
Ambient Temperature: 32 to 122°F (0 to 50°C). Some
degradation of display above 50°C.
Storage Temperature: -4 to 158°F (-20 to 70°C)
Relative Humidity: 10 to 90% (non-condensing)
Weight/Shipping Weight: 2 lb/3 lb (1 kg/1.5 kg)
Display: Two line, 16-character display. Character height:
4.8 mm; first line shows process variable (pH, ORP,
conductivity, % concentration, oxygen, ozone, chlo-
rine, or monochloramine), second line shows process
temperature and output current. For pH/chlorine com-
bination, pH may also be displayed. Fault and warn-
ing messages, when triggered, alternate with temper-
ature and output readings.
During calibration and programming, messages,
prompts, and editable values appear on the two-line
display.
Temperature resolution: 0.1°C (≤99.9°C);
1°C (≥100°C)
Hazardous Location Approval: For details, see specifi-
cations for the measurement of interest.
RFI/EMI: EN-61326
DIGITAL COMMUNICATIONS:
HART —
Power & Load Requirements: Supply voltage at the
transmitter terminals should be at least 12 Vdc.
Power supply voltage should cover the voltage
drop on the cable plus the external load resistor
required for HART communications (250 Ω mini-
mum). Minimum power supply voltage is 12 Vdc.
Maximum power supply voltage is 42.4 Vdc. The
graph shows the supply voltage required to
maintain 12 Vdc (upper line) and 30 Vdc (lower
line) at the transmitter terminals when the cur-
rent is 22 mA.
Analog Output: Two-wire, 4-20 mA output with
superimposed HART digital signal. Fully scalable
over the operating range of the sensor.
Output accuracy: ±0.05 mA
FOUNDATION FIELDBUS —
Power & Load Requirements: A power supply volt-
age of 9-32 Vdc at 13 mA is required.
Fieldbus Intrinsically Safe COncept/FISCO-compliant
versions of Model Xmt Foundation Fieldbus trans-
mitters are available.
Solu Comp is a registered trademark of Rosemount Analytical.
Xmt is a trademark of Rosemount Analytical.
HART is a registered trademark of the HART Communication Foundation.
FOUNDATION is a registered trademark of Fieldbus Foundation.
Sira MC070113/00