Installation manual

47
Reference Manual
00809-0100-4075, Rev CA
Appendix B: Product Certifications
March 2014
Product Certifications
European Certifications
I1 ATEX Intrinsic Safety
Certificate: Baseefa09ATEX0125X II 1G
Ex ia IIC T4(-50 °C T
a
70 °C)
IP66
1180
Special Conditions for Safe Use (X):
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
The enclosure is made of aluminium alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion if located in a
zone 0.
N1 ATEX Type n
Certificate: Baseefa09ATEX0131 II 3 G
Ex nA IIC T4 (-50 °C T
a
70 °C)
U
i
= 45 Vdc MAX
IP66
1180
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 09.0050X
Ex ia IIC T4(-50 °C T
a
70 °C)
IP66
Special Conditions for Safe Use (X):
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
The enclosure is made of aluminium alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion if located in a
zone 0.
Table B-1. Input Parameters
Loop power
U
i
= 30 V
I
i
= 200 mA
P
i
= 1.0 W
C
i
= 0
L
i
= 0
Table B-2. Input Parameters
Loop power
U
i
= 30 V
I
i
= 200 mA
P
i
= 1.0 W
C
i
= 0
L
i
= 0