Installation guide
Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
97
Verifying communication with the RNI
Use the ping command to verify that the RNI is responding:
1. At the AMS Device Manager PC, open a command prompt (Start > All Programs
> Accessories > Command Prompt).
2. At the command prompt, type PING <RNI DNS Name>. (If your network does
not support DNS, replace the DNS name with the IP address of your RNI in the
ping command.)
3. Press ENTER.
4. Verify that the RNI responds to the ping command. The ping command should
return a reply message.
5. If the ping command fails, verify that you typed the correct address in the
command line. Also verify that your network is functioning properly.
Configuring AMS Device Manager for an RS3 Interface
To configure AMS Device Manager for an RS3 interface:
1. Select Start > All Programs > AMS Device Manager > Network Configuration
from the Windows taskbar.
2. In the Network Configuration dialog, click Add.
3. In the Select Network Component Type dialog, select RS3 Network and click
Install.
4. Follow the RS3 Network Wizard instructions.
5. Start AMS Device Manager to set up the network structure. See “Determining
the system interface structure and device data” on page 108.
Note
Your installation is complete only after you receive a valid ping reply.