Installation guide
Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
91
7. In the Connection Properties dialog, select the Ovation System Parameters you
will be using.
• FOUNDATION fieldbus device support
• FOUNDATION fieldbus device alert support
• PROFIBUS DP device support
• WirelessHART device support
If you select WirelessHART device support, you must also identify the Smart
Wireless Gateway name and IP address, as well as enable secure
communications with the Wireless Gateway if you have installed the Security
Setup utility for the Smart Wireless Gateway.
8. The data fields in the Timings dialog contain default values which you cannot
change. Click Help for more information about the fields on this dialog.
9. Click Finish to complete the Ovation Network interface setup.
10. Click Close.
11. Start AMS Device Manager to set up the network structure. See “Determining
the system interface structure and device data” on page 108.
Note
Do not configure an AMS Device Manager Wireless System Interface if an Ovation System
Interface will be using the same wireless gateway.
Note
You must have computer administrator privileges to install an Ovation network.
Note
If you install both the Ovation System Interface and the FF HSE Interface on the same PC,
you must configure each on a unique IP address.
NOTICE
If an Ovation System Interface is removed and later re-added, any PROFIBUS DP
devices will need to be reidentified. To avoid this, back up your database before
removing the Ovation System Interface. After re-adding the interface, import the
backed up database.