Installation guide

AMS Suite: Intelligent Device Manager Installation Guide
NOVEMBER 2013
80
4. Follow the prompts in the Add Calibrator Wizard.
5. When finished, verify that the correct COM port is assigned by selecting the
calibrator name in the Network Configuration dialog and clicking Properties. If
necessary, change the COM Port on the Properties for the Calibrator dialog.
Connecting a documenting calibrator
For instructions on how to connect the calibrator to the PC, see the calibrator
documentation.
Connecting devices to a documenting calibrator
For instructions on how to connect devices to the documenting calibrator, see the
calibrator documentation.
HART Multiplexer Network Interface
With the optional HART Multiplexer Network Interface, AMS Device Manager can
communicate with HART devices through a HART multiplexer. HART multiplexers can
link many installed HART field devices to an AMS Device Manager PC, providing the
capability to remotely configure, troubleshoot, and monitor those devices. A typical
HART multiplexer network enables one PC COM port to communicate with up to 63
addressable HART multiplexers.
AMS Device Manager supports a variety of multiplexers, each with different
capabilities and requirements. Supported multiplexer types can have between 32
and 256 device connections. For a list of supported multiplexers, see the Release
Notes. For specific information about a supported multiplexer, see the
manufacturer’s documentation.
Note
This information refers to Arcom, Elcon, 8000 BIM, Spectrum Controls, Honeywell, and
Pepperl+Fuchs multiplexers. STAHL multiplexer interfaces are described on
page 38.
NOTICE
For the PC to communicate with a HART multiplexer, you must place either an RS-232
to RS-485 converter or a supported Ethernet serial hub between the multiplexer and
the PC. For supported peripherals, see the Release Notes.