Installation guide
AMS Suite: Intelligent Device Manager Installation Guide
NOVEMBER 2013
42
ABB
The ABB System Interface lets you use AMS Device Manager to view and configure
HART devices connected to I/O modules supported by the ABB System 800xA control
system.
AMS Device Manager Client SC or Server Plus software can be installed on an ABB
Station assuming PC hardware and software requirements are met, or on a separate
PC. The ABB Station must have the 800xA station software installed and configured
for AMS Device Manager to communicate with HART instruments connected using
the ABB Controller. The ABB System Interface requires:
• That the ABB Network is licensed in AMS Device Manager.
• That the ABB Station software version is 5.1 along with the “Performance Pack”
enhancement release from ABB.
• Use of the AC 800M series controllers.
• Use of the following supported HART IO modules
— AO815
— AI815
— AO895
— AI895
— AI880
— AO845
— AI845
• Use of the following supported multiplexers:
— Pepperl+Fuchs KFD2-HMM-16
— MTL4840
— Elcon Series 2700-F
— Elcon Series 2700-G