Installation guide

AMS Suite: Intelligent Device Manager Installation Guide
NOVEMBER 2013
38
RS3
The RS3 System Interface requires:
I/O hardware–FIC 4.8 or higher I/O cards with smart daughterboard and boot
revision supplied with P1R1.4 or MAIO FIM with 2.6 or higher
Controller hardware–MPC II Controller Processor or higher, CP-IV Coordinator
Processor or higher
System software–P1R3.4 or higher with controller image P1.10 or higher
Dedicated RNI–The RNI needs to be either version 4.1 (NT) or version 5.0 (XP or
Server 2003/2008). A single RNI will support multiple AMS Device Manager
connections.
STAHL
The STAHL HART interface requires:
RS-232/RS-485 converter for each network (see the Release Notes for
supported models)
STAHL ICS Module–9148 Multiplexer Module installed on a 9161 Module Board
with up to 16 HART Transmitter Supply Units (module 9103)
I.S.1 System–Central Unit Module 9440, Multiplexer Module 9461 (HART
analog input) or 9466 (HART analog output)
IS PAC 9192 HART multiplexer
The ICS Module is a single HART multiplexer that supports HART transmitter supply
units connected to field devices. The I.S.1 System routes messages to their
multiplexers with attached HART field devices. For additional information on
supported STAHL equipment, see the Release Notes and the manufacturer’s
documentation.
Note
AMS Device Manager and RS3 Operator Station (ROS), or DeltaV Operate for RS3 (DOR)
cannot be installed on the same PC.
Note
You may not be able to use AMS Device Manager to communicate with HART devices
through a STAHL IS PAC multiplexer at the same time a handheld communicator is
communicating with the device loop. See your STAHL representative for details.