Installation guide

Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
37
System software options–OWP with P1.2 or higher, PROVUE P5.5 or higher,
and ENVOX 3.4 or higher; I/O must be configured as “digital” or “hybrid”
Dedicated HDL with Ethernet connection (TCP/IP) to AMS Device Manager PC
FF HSE
The FF HSE interface requires:
One or more (up to 64) commissioned FF HSE Linking Devices that conform to
the F
OUNDATION fieldbus HSE and H1 specifications (for a list of supported
linking devices, see the Release Notes). The Remote Operations Controller for
F
OUNDATION fieldbus (ROC FF) and the ControlWave linking devices are
displayed in AMS Device Manager in the FF HSE hierarchy. For setup and
configuration of ROC FF and ControlWave linking devices, refer to the
documentation supplied with them.
Commissioning using the device manufacturer’s commissioning/
decommissioning utility.
FF HSE Linking Device configuration with unique TCP/IP addresses.
An AMS Device Manager station with 1 or 2 Ethernet network interface cards
(NIC). A NIC dedicated to the FF HSE segment is recommended to reduce the
amount of competing network communications.
Note
All linking devices on the same network must have unique tag names. If duplicate tag
names are used, the hierarchy will not build properly.
NOTICE
If you have an Ovation network installed, use a different TCP/IP address for the FF HSE
network.