Installation guide
Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
35
— To receive FOUNDATION fieldbus device alerts in AMS Device Manager, the
Ovation OPC Alarm and Event Server package must be installed on your
co-deployed Ovation/AMS Device Manager station. The AMS Device
Manager Ovation System Interface must also be installed on this station.
• For WirelessHART devices:
— If you want to access information for WirelessHART devices on an Ovation
system, configure an Ovation System Interface in AMS Device Manager
with WirelessHART support enabled and a connection to a Smart Wireless
Gateway configured.
• For PROFIBUS DP devices:
— If you want to access information for PROFIBUS DP devices on an Ovation
3.3.1 or later system, configure an Ovation System Interface in AMS
Device Manager with PROFIBUS DP support enabled.
— PROFIBUS DP devices will only be supported on Ovation 3.3.1 or later
networks. A PROFIBUS DP module can contain up to 2 ports. Each port
can be connected to up to 124 PROFIBUS DP devices. For Ovation 3.3.1, a
patch (OVA331027) is required.
• For SIS devices:
— If you want to access SIS HART device information on your Ovation system
through AMS Device Manager, AMS Device Manager can be configured on
an Ovation Station or on a non-Ovation Station. Use the AMS Device
Manager Network Configuration utility to set up an Ovation System
Interface.
Note
Some FOUNDATION fieldbus devices have a feature known as “reannunciation” (or
“multibit”). This feature must be disabled for devices on an Ovation 3.5 system so that AMS
Device Manager can receive alerts from these devices. This feature is typically enabled/
disabled in the AMS Device Manager device Configure/Setup properties screens (the exact
location varies by device).
Note
If you install AMS Device Manager and configure an Ovation System Interface on a PC that
is not an Ovation Station and try to access HART devices, performance will be significantly
impacted if the hosts file on the AMS Device Manager station is missing specific entries. To
improve performance, add the IP address and hostname for each configured Ovation
Safety Data Server to the C:\WINDOWS\SYSTEM32\DRIVERS\ETC\HOSTS file on the AMS
Device Manager Station.