Installation guide

Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
103
Kongsberg Maritime
The Kongsberg System Interface lets you use AMS Device Manager to communicate
with HART devices using I/O modules supported by the Kongsberg Maritime System.
The Kongsberg Network communicates with HART devices using the Kongsberg
Automation Server which is an application with a Web Service interface.
The Kongsberg Network is deployed where there is access to the Kongsberg
Automation Server with IIS. It is not necessary to install the Kongsberg Automation
Server on an AMS Device Manager station, however, communications performance is
better with this deployment type. For deployment scenarios that require AMS Device
Manager Client Stations to cross External Firewalls, refer to KBA NA-0400-0046.
If you install additional Kongsberg Networks, they must be linked to unique
Automation Server URLs. The Kongsberg Network supports communications with
HART instruments connected to STAHL ISPac HART Multiplexers and STAHL
PROFIBUS DP Remote I/O modules for HART. The Kongsberg Interface supports
Advanced Valve Diagnostics using the AMS ValveLink SNAP-ON application.
Configuring AMS Device Manager for a Kongsberg
System Interface
To configure AMS Device Manager for a Kongsberg System Interface:
1. Select Start > All Programs > AMS Device Manager > Network Configuration
from the Windows taskbar.
2. Click Add.
3. In the Select Network Component Type dialog, select Kongsberg Network and
click Install.
4. Follow the Kongsberg Network Wizard instructions.
5. Choose the Kongsberg Automation Server URL. The URL connection to the
Automation Server is tested and if not found, a corresponding message is
displayed.
6. If the URL connection is found, click Finish.
7. Close the Network Configuration dialog.
8. Start AMS Device Manager. See “Determining the system interface structure
and device data” on page 108.
Preparing the Kongsberg control system